SPECIFICATIONS
MODEL
ITEMS
℃
-20 - +60°C (-20 - +50°C:100%, +60°C:70%)
20 - 95%RH (No Condensing)
20 - 95%RH (No Condensing)
I/P - O/P, I/P - FG : 2kVAC (10mA) for 1min.,
O/P - CNT(RC) : 100VAC (100mA) for 1min.
O/P - FG : 500VDC 100Mohm, O/P - CNT(RC) : 100VDC 10Mohm
Designed to meet JIS E 3014-2-B
Designed to meet JIS E 3015-2-B
Approved by UL60950-1 & CSA60950-1,
Designed to meet EN60950-1
Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A
Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A
Designed to meet IEC61000-4-2(Level 2,3), -4(Level 3), -8(Level 4)
38 x 95 x 130 ( Refer to Outline Drawing )
*Read instruction manual carefully, before using the power supply unit.
At 24VDC, Ta=25°C, nominal output voltage and maximum output power.
Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz.
18 - 32VDC, constant load.
No load-Full load, constant input voltage.
OCP TYPE : Constant current limit with automatic recovery.
OVP circuit will shut the output down, manual reset (Re power on).
- Derating at standard mounting. Refer to output derating curve(B027-01-02_).
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
At 24VDC Input.(Refer to instruction manual.)
1.6
RDS30-24-5 RDS30-24-12 RDS30-24-15 RDS30-24-24