TN-1500-212B

SPECIFICATION
TN-1500-112 TN-1500-124 TN-1500-148 TN-1500-212 TN-1500-224 TN-1500-248
200 / 220 / 230 / 240VAC selectable by setting button S.W
50 0.1Hz 50/60Hz selectable by setting button S.W±
75A
24V
21 ~ 30VDC
89%
37.5A
48V
42 ~ 60VDC
89%
75A
24V
21 ~ 30VDC
90%
37.5A
48V
42 ~ 60VDC
91%
MODEL
WAVEFORM
Note.2
OUTPUT
FREQUENCY
AC REGULATION (Typ.)
TRANSFER TIME (Typ.)
FRONT PANEL INDICATOR
SAVING MODE (Typ.)
NO LOAD DISSIPATION (Typ.)
BAT. VOLTAGE
OFF MODE CURRENT DRAW
VOLTAGE RANGE (Typ.)Note.3,6
EFFICIENCY (Typ.) Note.2
DC CURRENT (Typ.) Note.5
INPUT
INPUT
PROTECTION
BATTERY
OUTPUT
FUSE
SAFETY &
EMC
BAT. LOW ALARM
BAT. LOW SHUTDOWN
OVER TEMPERATURE
OUTPUT SHORT
REVERSE POLARITY
GFCI PROCTECTION
100 / 110 / 115 / 120VAC selectable by setting button S.W
1725W for 180 sec. / 1875W for 10 sec. / surge power 3000W for 30 cycles
True sine wave (THD<3%)
60 0.1Hz 50/60Hz selectable by setting button S.W±
150A
12V
10.5 ~ 15VDC
88%
40A*5 30A*3 30A*2
30A*230A*3
11.3 4%±
22.5 4%± 45 4%±45 4%±22.5 4%±
10.5 4%± 21 4%± 42 4%±42 4%±21 4%±
±3.0%
10ms inverter by pass
Default disabled. Load 5W will be changed to standby mode
Battery voltage level, output load level, saving mode, fault and operation status
18W @ standby saving mode
12V
1mA
10.5 ~ 15VDC
87%
150A
40A*5
11.3 4%±
10.5 4%±
82 5℃±
Protection type : Shut down o/p voltage, re-power on to recover ; by internal RTH3 detect on heatsink of power transistor
Protection type : Shut down o/p voltage, re-power on to recover
82 5℃± 96 5℃± 68 5℃± 68 5℃± 68 5℃±
By internal fuse open
Optional (Only type F) None
10A
Compliance to FCC class A, EAC TP TC 020
Compliance to EAC TP TC 020
WORKING TEMP. Note.1
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
LVD
SAFETY STANDARDS
0 ~ +40 @ 100% load ; 60 @ 50% load
℃℃
20% ~ 90% RH non-condensing
-30 ~ +70 / -22 ~ +158 F, 10 ~ 95% RH non-condensing
o
None
EN60950-1
Compliance to EN61000-4-2,3,4,5,6,8,11, EAC TP TC 020
Compliance to EN55032 class B, 72/ 245/ CEE, 95/ 54/ CE, E-Mark, EAC TP TC 020
True sine wave output (THD<3%)
High surge power up to 3000W
U.P.S. mode and energy saving mode (selectable)
High efficiency up to 91%
Power ON-OFF switch
Standby saving mode can be selectable
Front panel indicator for operation status
Thermostatically controlled cooling fan
Protections: Bat. low alarm / Bat. low shutdown / Over voltage / Over temp.
/ Output short / Input polarity reverse / Overload / AC circuit breaker
Application : Home appliance, power tools, office and portable
equipment, vehicle and yacht ...etc.
Built-in solar / AC charger
Computer-based monitoring software (Note.7)
3 years warranty
RATED POWER (Typ.) 1500W
BATTERY TYPES
Open & sealed Lead Acid
OVER LOAD (Typ.)
CIRCUIT BREAKER
105 ~ 115% load for 180 sec., 115% ~ 125% load for 10 sec.
Protection type : Shut down o/p voltage, re-power on to recover
15A
WITHSTAND VOLTAGE
Bat I/P - AC I/P:3.0KVAC Bat I/P - AC O/P:3.0KVAC AC O/P - FG:1.5KVAC
VIBRATION
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
U 458 (L only for "GFCI" receptacle-Type F ), EAC TP TC 004
Features :
1500W True Sine Wave DC-AC Inverter with Solar Charger
TN-1500 series
MAX OPEN CIRCUIT VOLTAGE
CHARGE CURRENT (Typ.)
CHARGE CURRENT (max.)
CHARGE VOLTAGE
CHARGE VOLTAGE
25V
5.5A
30A
14.3V 4±
%
14.3V 4± %
SOLAR
CHARGER
AC
CHARGER
28.5V 4±
%
28.5V 4± %
2.7A
75V
57V 4%±
57V 4±
%
1.35A
EAC TP TC 004
45V
28.5V 4±
%
28.5V 4± %
2.7A
75V
57V 4±
%
57V 4± %
1.35A
14.3V 4±
%
14.3V 4± %
5.5A
45V
25V
OTHERS
PACKING
6.85Kg; 2pcs/15.7Kg/1.61CUFT
DIMENSION
CONTROL WIRING Note.7
420*220*88mm (L*W*H)
RJ11 -RS232
NOTE
1.Output derating capacity referenced by curve 1.
2.THD and Efficiency is tested by 1000W, linear load at 13V, 26V, 52V input voltage.
3.Input derating capacity referenced by curve 2.
4.All parameters not specified above are measured at rated load, 25 of ambient temperature and set to factory setting.
5.DC current is tested by 1500W, linear load at 13V, 26V, 52V input voltage.
6.The tolerance of each voltage value by models is:112/212 0.5V;124/224 1V;148/248 2V.
→± →± →±
7.The cable is enclosed for the connection between TN-1500 and computer for software monitoring.
8.Please do not turn on the inverter before start the engine if inverter connect to vehicle’s battery directly.
9.The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
AC VOLTAGE
Factory setting set at 110VAC Factory setting set at 230VAC
PROTECTION
ENVIRONMENT
MAXIMUM OUTPUT POWER (Typ.)
E
13
EMC IMMUNITY
EMC EMISSION
File Name:TN-1500-SPEC 2018-01-15
Inverter TN V.1.1
3. Installation of TN-1500 unit and PC
4. Explanation of Monitoring Manu
4.1 Main Page
Figure 2
1. Setting: Adjustment for output voltage, charging related voltage, frequency, and operation mode. Please refer to Figure 3 for details.
2. Statistics: Calculate for the percentage of operating period for each operation mode. Please refer to Figure 4 for details.
3. R.C. Power off: Power can be turned ON or OFF at the remote location.
4. Pause: Stop refreshing the page of monitoring software.
5. Status of unit: Indicating current operating status of TN-1500.
6. Signals that display current condition of the unit.
DB9 FEMALE
Figure 1
1
6
Phone Jack
RJ11
RJ11
PIN NO.
DB9
PIN NO.
2
3
3
5
4
2
1
2
3
4
6
7
8
9
5
Setting
Solar Charge
1234
5
6
INVERTER
AC Charge
100 100
00
Battery Voltage
O/P Voltage
Internal Temperature
By pass
TN-1500-143
Utility Voltage
Start Date
Reset Date
O/P Frequency
Power on
Remote off
Battery low
Battery used up
Stand by saving mode
Abnormal Shutdown
Battery Loading
54.1
110
10.0
0.0
2007/12/07 03:13:33 PM
2007/12/21 01:40:56 PM
60.0
V
V
V
Hz
AC In
Statistics R.C. Power off Pause Exit
1. The monitoring software can be downloaded from product section (with TN-1500 specification) on MEAN WELL’s official website,
2.The monitoring software can run on Windows 7 English version, Windows 7 Chinese (Traditional, Taiwan) version, Windows 8 English version
http://www.meanwell.com
and Windows 8 Chinese (Traditional, Taiwan) version
File Name:TN-1500-SPEC 01-152018-
1500W True Sine Wave DC-AC Inverter with Solar Charger
TN-1500 series
Instructions for TN-1500 monitoring software
Inverter Setting
Inverter Setting
4.2 Setting Page
4.3 Statistic Page
Figure 3
Figure 4
1. User can adjust the settings based on the characteristics of batteries been used: Equalization Voltage, Floating Voltage, Alarm Voltage,
and Shut-down Voltage. UPS Mode / Energy Saving Mode selection and AC output voltage and frequency can also be set in this page.
2. Read: Read current settings of the unit.
3. Write: Write the revised setting into the unit.
4. Load: Load in factory default settings.
1. Start Date: Date that installing the monitoring software.
2. Reset Date: Date that resetting the statistics. The Start Date will not be influenced by resetting the statistics or turning off the unit.
3 .Inverter time rate: Operating period of "Inverter Mode" represents how many percent of the whole operating period.
4. Bypass time rate: Operating period of "Bypass Mode" (energy provides directly by the utility) represents how many percent of the whole
operating period.
5. Shut down rate: Percentage of time period that the unit is under the condition of shut down.
* Inverter time rate + Bypass time rate + Shut down rate = 100%
6. Solar time rate: Percentage of time period that the solar charger is functioning after turning on the TN-1500 unit.
7. Loading average: Average loading after turning on the TN-1500 unit.
1
File Name
Model name
Manufacture Series Number
Date Of Manu.Revision
I/O Type
Bauds Rate
Equalization Volt.
Floating Volt.
Alarm Volt.
Shutdown Volt.
Voltage
Frequency
Stand-by saving mode
UPS mode
Energy saving mode
D:\TN_110RR\20071205\REV\TN_110RR\TNF\TN_1K5_512.TNF
Start Date Start Date2007/12/07 03:13:33 PM 2007/12/21 01:40:56 PM
Inverter time rate Inverter time rate
Bypass time rate Bypass time rate
Shut Down rate Shut Down rate
Solar time rate Solar time rate
Loading average Loading average
91.2 31.9
0.0 0.0
8.8 68.1
0.0 0.0
24.7 63.7
%%
%%
%%
%%
%%
TN-1500-212
MeanWell LOC-1234567890
REV:1.10
212
9600
14.3
13.3
11.3
10.5
V 13.5 ~ 15.0V
13.0 ~ 13.5V
11.0 ~ 11.5V
10.0 ~ 11.0V
V
V
V
230 V
50
1
Read Write Lead Exit
Read OK!!
Hz
On
On
On
Comm Ports
23 4
Off
06/23/2007
1500W True Sine Wave DC-AC Inverter with Solar Charger
TN-1500 series
File Name:TN-1500-SPEC 01-152018-
ExitRESET

TN-1500-212B

Mfr. #:
Manufacturer:
Description:
Power Inverters 1500W 12VDC 230VAC Solar Charger, GFCI
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS