AXL F AI4 U 1H
8659_en_03 PHOENIX CONTACT 16
14.4.1 Diagnostics state (0018
hex
: DiagState)
This object is used for a structured message of an error.
Error and status of the local status and diagnostics indicators
0018
hex
: DiagState (Read)
Subindex Data type Length in
bytes
Meaning Contents
0 Record 21 Diagnostic state Complete diagnostics information
1 Unsigned 16 2 Error number 0 ... 65535
dez
2 Unsigned 8 1 Priority 00
hex
No error
01
hex
Error
02
hex
Warning
81
hex
Error removed
82
hex
Warning eliminated
3 Unsigned 8 1 Channel/group/module 00
hex
No error
01
hex
Channel 1
::
04
hex
Channel 4
FF
hex
entire device
4 Unsigned 16 2 Error code See table below
5 Unsigned 8 1 More follows 00
hex
6 Visible String 14 Text (14 characters) See table below
The message with the priority 81
hex
or 82
hex
is
a one-time internal message to the bus cou-
pler that is implemented onto the error mech-
anisms of the higher-level system by the bus
coupler.
Subindex 2 3 4 6
Error Pri-
ority
Chan-
nel/
group/
module
Error code Text Process
data
LED
hex hex hex D UA E1 E2
No error 00 00 0000 Status OK xxxx Green ON ON OFF OFF
Supply voltage faulty
(supply for analog mod-
ules U
A
)
01 FF 5160 Supply fail 8020 Flashing
green/yellow
OFF ON ON
Device error 01 FF 6301 CS FLASH 8040 Green ON ON OFF ON
Flash format error 01 FF 6302 FO FLASH 8040 Green ON ON OFF ON
Parameter table invalid 01 FF 6320 Invalid para 8010 Green ON ON OFF ON
Overrange 02 01 ... 04 8910 Overrange 8001 Green ON ON OFF ON
Underrange 02 01 ... 04 8920 Underrange 8080 Green ON ON OFF ON
AXL F AI4 U 1H
8659_en_03 PHOENIX CONTACT 17
14.4.2 Reset diagnostic mesages (0019
hex
: ResetDiag)
You can delete the diagnostics memory and acknowledge the diagnostic messages with this object.
14.5 Objects for process data management
IN process data (0025
hex
: PDIN)
You can read the IN process data of the module with this object.
The structure corresponds to the representation in the "Process data" section.
0019
hex
: ResetDiag (Write)
Subindex Data type Length in
bytes
Meaning Contents
0 Unsigned 8 1 Reset diagnostics 00
hex
All diagnostic messages approved
02
hex
Deletes and acknowledges all
pending diagnostic messages that
have not been read out
06
hex
Deletes and acknowledges all the
diagnostic messages and allows no
further diagnostic messages
Other Reserved
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
0025 PDIN Var Octet string 1 8 R Input process data
0026 PDOUT Var Octet string 1 8 R OUT process data; not applicable
003B PDIN_Descr Record 3 12 R Description of the IN process data
003C PDOUT_Descr Record 3 12 R Description of the output process data
Objects 003B
hex
and 003C
hex
are only appli-
cable to tools and are therefore not described
in more detail here.
Please refer to the basic profile for compre-
hensive information.
0025
hex
: PDIN (Read)
Subindex Data type Length in bytes Meaning
0 Octet string 8 Input process data
AXL F AI4 U 1H
8659_en_03 PHOENIX CONTACT 18
14.6 Objects for device management
These objects are available as of firmware 1.10.
14.6.1 Reset parameterization (002D
hex
: ResetParam)
This object is used to reset the module to the default set-
tings.
To reset the module value 01
hex
must be transferred during
write access. Any other values are not permissible and will
be acknowledged with an error.
Then the default settings of the channels are loaded and all
the user-set parameters are reset.
14.6.2 Checksum (002E
hex
: Checksum)
The data of the startup objects is verified with this CRC32
checksum.
Index
(hex)
Object name Object
type
Data type A L Rights Meaning
002D ResetParam Simple
variable
Unsigned 8 1 1 R/W Reset parameterization
002E CheckSum Simple
variable
Unsigned 32 1 4 R Checksum
Checksum for the default setting: 9C 09 21 54