TRIO-PS/ 1AC/12DC/10 Order No.: 2866488
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866488
PHOENIX CONTACT Inc., USA Page 4 / 6
http://www.phoenixcon.com Oct 8, 2010
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
Surge voltage category III
Connection data, input
Type of connection Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 9 mm
Screw thread M2,5
Connection data, output
Type of connection Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 9 mm
Signaling
Status display "DC OK" LED green
Note on status display U
OUT
< 0.9 x U
N
: LED flashing
Certificates / Approvals
Certification CUL, CUL Listed, UL, UL Listed