PDU12IEC

1.6/3.8kW Single-Phase 100–240V Basic PDU, 14
Outlets (12 C13 & 2 C19), C20 16A Input, 1U
Rack-Mount
MODEL NUMBER: PDU12IEC
Delivers 100–240V single-phase AC power to multiple loads from a utility outlet, generator or UPS system
in a high-density IT environment. Ideal for networking, telecom, security, audio/video and sound
reinforcement applications.
Description
The PDU12IEC 1.6/3.8kW Single-Phase 100–240V Basic PDU is the perfect no-frills unit for networking,
telecom, security, audio/video and sound reinforcement applications. Perfectly suited for high-density IT
environments, the PDU12IEC features a single load bank with 14 total outlets—eight rear C13, two rear
C19 and four front C13. The C20 inlet accepts a variety of user-provided power cords that connect to your
facility’s compatible AC power source, generator or protected UPS to distribute power to connected
equipment.
The switchless design prevents an accidental shutdown, which could lead to costly downtime. Dual 16A
circuit breakers protect connected equipment from dangerous overloads. The reversible all-metal housing
mounts in 1U of space in EIA-standard 19-inch racks, as well as on a wall or workbench or under a
counter. With a compatible rack and Tripp Lite’s PDUSIDEBRKT accessory (sold separately), you can
adapt the PDU12IEC for vertical 0U rack-mounting.
Features
Reliable Single-Phase Power Distribution
Ideal no-frills PDU for networking, telecom, security, audio/video and sound reinforcement applications
14 total outlets—8 rear C13, 2 rear C19 and 4 front C13—in one load bank
Built-in 16A circuit breakers protect outlets against overloads
C20 inlet accepts wide variety of user-supplied power cords
Rear-panel grounding lug
Highlights
C20 inlet accepts wide variety of
user-supplied power cords
14 total outlets—8 rear C13, 2
rear C19 and 4 front C13
Switchless design prevents
accidental shutdown
Reversible all-metal housing
Installs in rack, on wall or under
counter
Package Includes
PDU12IEC 1.6/3.8kW Single-
Phase 100–240V Basic PDU
Mounting hardware
Owner’s manual
1 / 3
Specifications
Switchless Design
Prevents accidental shutdowns and costly downtime
Versatile Installation Options
Mounts horizontally in 1U of EIA-standard 19 in. 2- and 4-post racks
Reversible all-metal housing faces front or rear in rack
Ready for toolless 0U vertical installation with optional PDUSIDEBRKT (sold separately)
Also mounts on wall, workbench or under a counter
OVERVIEW
UPC Code 037332116253
PDU Type Basic
OUTPUT
Output Capacity Details 3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V), 2.03kW (127V), 1.92kW (120V),
1.6kW (100V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (12) C13; (2) C19
Output Nominal Voltage 100; 120; 127; 200; 208; 220; 230; 240
Overload Protection 16A circuit breaker
INPUT
PDU Input Voltage 100; 120; 127; 200; 208; 220; 230; 240
Recommended Electrical Service 20A 120V; 20A 208/240V; 16A 230V
Maximum Input Amps 16
PDU Plug Type IEC-320 C20
Input Cord Details C20 inlet accepts user supplied input cable with C19 output connection
Input Phase Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Switches No power switch
PHYSICAL
Minimum Required Rack Depth
(inches)
7.8
Minimum Required Rack Depth (cm) 19.81
2 / 3
© 2018 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
https://www.tripplite.com/products/product-certification-agencies
Shipping Dimensions (hwd / in.) 2.10 x 20.60 x 9.30
Shipping Dimensions (hwd / cm) 5.33 x 52.32 x 23.62
Shipping Weight (lbs.) 3.70
Shipping Weight (kg) 1.68
Unit Dimensions (hwd / in.) 1.75 x 17.5 x 4.25
Unit Dimensions (hwd / cm) 4,4 x 44,5 x 10,8
Unit Weight (lbs.) 3.20
Unit Weight (kg) 1.45
Material of Construction Metal
Form Factors Supported 1U rackmount, 0U vertical rackmount, wall-mount and undercounter installation supported
PDU Form Factor Horizontal (1U)
Outlets Measurement (Center to
Center)
Distance between Front (C13) outlets = 28.75mm; Distance between Rear (C19) outlets = 55mm; Distance between
Rear (C13) outelts = 28.75mm
ENVIRONMENTAL
Storage Temperature Range 5 to 122F (-15 to 50C)
Relative Humidity 5-95% non-condensing
Operating Elevation (ft.) 0-10,000
Operating Elevation (m) 0-3000
SPECIAL FEATURES
TVSS Grounding Back panel grounding lug
CERTIFICATIONS
Certifications Tested to UL60950-1 (USA) and CAN/CSA C22.2 No. 60950-1-03 (Canada), CE (Europe)
WARRANTY
Product Warranty Period
(Worldwide)
5-year limited warranty
3 / 3

PDU12IEC

Mfr. #:
Manufacturer:
Tripp Lite
Description:
Power Outlet Strips PDU 100V-240V 16A C13/C19/C20 Horz1URM
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet