8345-F01A-S3M0-DB1B4B-45A-V

Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
www.e-t-a.com06/07(101106)
3 - 27
3
Current Trip curves and internal resistance () per pole
rating (A) K1, M1, T1, K2, M2, T2
0.05 452 376
0.1 100 94
1 0.95 0.90
2 0.26 0.20
3 0.10 0.10
5 0.042 0.040
10 < 0.02 < 0.02
15 < 0.02 < 0.02
20 < 0.02 < 0.02
25 < 0.02 < 0.02
30 < 0.02 < 0.02
40 < 0.01 < 0.01
50 < 0.01 < 0.01
60 < 0.01 < 0.01
80 < 0.01 < 0.01
100 < 0.01 < 0.01
125 < 0.01 < 0.01
Description
Typical applications
Approvals
Technical data
Single or multipole hydraulic-magnetic circuit breakers with trip-free-
mechanism and toggle actuation. A choice of switching characteristics
ensures suitability for a wide range of applications. Industry standard
dimensions and panel mounting. Auxiliary contacts optional. Low
temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934) S-type HM CBE.
In the business fields Communication and Transport: power supplies,
switchgear, instrumentation and process control engineering.
8345
1-pole 2-pole
Voltage rating 3 AC 415 V; AC 277/480 V;
AC 120/240 V; AC 240 V; DC 80 V,
Current rating range 0.05...125 A single and multipole
150...180 A single pole, two poles
connected in parallel
higher ratings upon request
Auxiliary circuit AC 240 V 6 A; DC 28 V 3 A
DC 65 V 1 A; DC 80 V 0.5 A
Typical life 10,000 operations at 1 x I
N
Ambient temperature -40...+85 °C (-40...+185 °F)
Insulation co-ordination
(IEC 60664) 2.5 kV/2
reinforced insulation in operating area
Dielectric strength test voltage
operating area AC 3,000 V
pole to pole AC 1,500 V
main to auxiliary circuit AC 3,000 V
switching to trip circuit AC 1,500 V
Insulation resistance > 100 M(DC 500 V)
Degree of protection operating area IP40
(IEC 60529) terminal area IP00
Vibration
with toggle down: 10 g (57-2000 Hz) ±0,76mm (10-57Hz)
at 0.9 I
N
directions 1, 2, 3, 4, 5: 10 g at 1 x I
N
with curves F1, F2: 10 g at 0.8 x I
N
in all planes.
(57-2000 Hz) ±0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
directions 1, 2, 3, 4, 5: 100 g (11 ms) at 1 x I
N
,
direction 6: 100 g (11 ms) at 0.8 x I
N
,
with curves F1, F2: 100 g (11 ms) at 0.8 x I
N
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5% salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
Mass approx. 90 - 120 g per pole
depending on version
VDE (EN 60934) 1- to 6-pole
UL 489
UL 1077 1- to 6-pole
CCC 1- to 4-pole
Standard current ratings and typical internal resistance values
Interrupting capacity
to EN 60934, UL 489 and UL 1077
IEC 60934 – test series E
voltage number of poles I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.02...125 10,000
AC 240/415 V 1 - 6 0.02...80 6 x I
N
AC 240 V 1 0.02...20 5,000
UL 489 – test sequence Z
voltage number of poles I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.5...125 10,000
AC 120 V 1 0.5...80 5,000
AC 120/240 V 1 0.5...80 5,000
AC 240 V 1 (2) 0.5...20 5,000
UL 1077
voltage number of poles I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.02...125 10,000
AC 277/480 V 1 - 6 0.02...70 5,000
www.e-t-a.com 06/07
(101106)
3 - 28
Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
3
Type number
X8345
Module
S auxiliary contact module
Auxiliary contacts
01 in all poles
02 in pole 1 only
03 in poles 1 + 3 only
04 in pole 2 only
Auxiliary contact version
H auxiliary contacts standard, gold-flushed
(asymmetrical terminals not for UL 489)
K auxiliary contacts, tin-plated (symmetrical terminals)
Auxiliary contact function
W1 1 changeover
W2 2 changeover
Terminal design
02 microswitch with blade terminals
DIN 46244-A2.8-0.5
M mounted to base unit
X8345 - S 01 H W1 02 M ordering example
Ordering information for auxiliary contact module
Ordering information
Type No.
8345
Mounting
B flange mounting, with rectangular aperture with mounting nut 6-32UNC
C flange mounting, with rectangular aperture with mounting nut M3
E flange mounting, with round aperture with mounting nut 6-32UNC
F flange mounting, with round aperture with mounting nut M3
Configuration
0 without barrier
1 with small barrier
2 with large barrier (request for multipole AC applications with
approvals to UL 489, UL 1077, IEC)
Number of poles
0 single pole unprotected
1 single pole protected
2 two pole protected
3 three pole protected
4 four pole protected
P one pole protected, two poles connected in parallel
characteristic curves E/H/R upon request
Q one pole protected, three poles connected in parallel
characteristic curves E/H/R upon request
R one pole protected, four poles connected in parallel
characteristic curves E/H/R upon request
S one pole protected, five poles connected in parallel
characteristic curves E/H/R upon request
Actuator configuration
A all poles with standard toggle
B reduced number of standard toggles
Z without actuator
Terminal design
L screw terminals M5 ≤ 50 A
M solder terminals ≤ 75 A
P blade terminals ≤ 35 A
R round connectors 6 mm
S stud terminals M5 ≤ 60 A
T stud terminals 10-32UNF-3A ≤ 60 A
U stud terminals M6 ≤ 125 A
V stud terminals 1/4-20UNC-3A ≤ 125 A
W laminated round terminals ≤ 125 A
Terminal hardware
0 without
3 with washer and nut
6 Phillips screws
Characteristic curve
K1 short delay DC
K2 short delay AC
M0 medium delay AC/DC
M1 medium delay DC
M2 medium delay AC
Q0 switch only
T1 long delay DC
T2 long delay AC
Illumination
- without
Version
D standard
Colour configuration
B1 black actuator
B2 white actuator
B8 blue actuator
Marking
front plate actuator base
A1 without without
A2 I
N
without
A3 I
N
, characteristic curve without
A4 I
N,
characteristic curve, without
wiring diagram on side
B1 without ON-OFF
B2 I
N
ON-OFF
B3 I
N
ON-OFF
characteristic curve
B4 I
N
, characteristic curve, ON-OFF
wiring diagram on side
8345 - C 0 1 A - U 3 M1 - . D B1 A1 ...
8345 - C 0 1 A - U 3 M1 - . D B1 A1
Rated voltage
B AC or ≤ 80 V DC
C DC ≤ 80 V
AC ≤ 277 V
(only for configurations
0 and 1)
Current ratings
0.05...125 A
higher current ratings
upon request
Approvals (optional)
V UL 489
8345 - C 0 1 A - U 3 M1 - . D B1 A1 B - 60 A - . ordering example
Remote trip coil available to special order!
Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
www.e-t-a.com06/07(101106)
3 - 29
3
O
F
F
O
F
F
O
F
F
Z
without toggles
B
reduced number of toggles per unit, mounting version B/C
A
1 toggle per pole, mounting version B/C
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
B
reduced number of toggles per unit, mounting version E/F
A
1 toggle per pole, mounting version E/F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
O
F
F
Actuator configuration
LOAD LINE
Mounting version E/F
Flange mounting round aperture
Cut-out dimensions:
48
63.5
28.6
Mounting version B/C
Flange mounting rectangular aperture
2.50
pole
19.1 ± 0.1
12 34
number of poles 1 to 4
mounting thread M3 or 6-32
all dimensions referred to the top edge
mounting depth 4.2 mm/.165 in.
max. insertion depth 5.5 mm
max. tightening torque 0.33 Nm
1.89
1.13
Cut-out dimensions:
1-pole multipole
52.4
36.8
11
19.2
ø4
.157
1.45
2.06
.433
.756
28.7
47.7
9.6
2.63
1.88
.378
1.13
66.8
76.5
3.01
ø15.4
3.5
±
0.1
(M3)
4
+0.1
-0.15
(6-32UNC)
15.45
1-pole
.606
.138
±
.004
(M3)
.157
+.004
-.006
(6-32UNC)
.608
44.75
1.76
4-pole
38.2
57.3
ø15.4
.606
1.50
2.25
ON
OFF
67.7
2.67
48
63.5
28.6
2.50
1.89
1.13
LOAD LINE
67.7
2.67
ON
OFF
pole
12 34
number of poles 1 to 4
mounting thread M3 or 6-32
all dimensions referred to the top edge
mounting depth 4.2 mm/.165 in.
max. insertion depth 5.5 mm
max. tightening torque 0.33 Nm
.752 ± .004
19.2
.756
n x 19.2
n x .756
19.1 ± 0.1
.752 ± .004
3.5
±
0.1
(M3)
4
+0.1
-0.15
(6-32UNC)
.138
±
.004
(M3)
.157
+.004
-.006
(6-32UNC)
19.2
.756
n x 19.2
n x .756
Dimensions Installation drawing
mounting
area
operating area
(reinforced insulation)
terminal
area
.039
1.14
1.77
.315
.079
.079
1
8
45
29
2
2
LOAD
LINE
This is a metric design and millimeter dimensions take precedence (
mm
)
inch

8345-F01A-S3M0-DB1B4B-45A-V

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union