VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage Correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage Correction Input voltages between 92 and 107 are boosted by 14%
Severe Undervoltage Correction Input voltages between 75 and 92 are boosted by 30%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Backlighted LCD screen offers detailed UPS status information, configuration options and Error message reporting;
STATUS INFORMATION includes Input Voltage, Output Voltage, Estimated Runtime (minutes), Output Load
Percentage, Output Load Wattage, Battery Charge Percentage, Graphical 5-Bar Battery Charge Level and UPS
Operating Mode Display / CONFIGURATION OPTIONS include Power Sensitivity, LCD Status Information Scrolling,
Alarm Disable, LCD Brightness and Self Test / REPORTED ERROR MESSAGES include Replace-Battery and
Overload conditions; LCD Screen rotates for vertical or horizontal UPS placement
Switches ON/OFF/MODE button provides UPS on/off power control (long-press) and advances the LCD screen display (short
tap); MUTE/ENTER button provides temporary alarm cancel, plus selection and confirmation of on-screen
configuration options
Alarm Cancel Operation Press the MUTE/ENTER button during a power failure to silence the alarm; Once silenced, alarm will re-sound to
indicate low-battery status
Audible Alarm Audible alarm indicates power-failure and low-battery status; Alarm can be disabled entirely via front panel LCD
interface (see manual)
LED Indicators Front panel LCD display
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 870
UPS AC Suppression Response
Time
Instantaneous
UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
UPS Dataline Suppression Details 168 joules; Compatible with POE applications
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description
Pair of mounting ears enable tower and 2-4 post rackmount installation
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.)
3.49 x 17.33 x 10.5
UPS Power Module Dimensions
(hwd, cm)
8.86 x 44.02 x 26.67
Rack Height (U Spaces) 2
Minimum Required Rack Depth
(inches)
13.5
Minimum Required Rack Depth (cm) 34.29
UPS Power Module Weight (lbs.) 26.56
4 / 6