FLK-1663 UK

4 Fluke Corporation 1660 Series Multifunction Installation Testers
Test Voltage Insulation Resistance Range Resolution Test Current
50 V 20 M/50 M 0.01 M/0.1 M 1 mA @ 50 k
100 V 20 M/100 M 0.01 M/0.1 M 1 mA @ 100 k
250 V 20 M/200 M 0.01 M/0.1 M 1 mA @ 250 k
500 V 20 M/200 M/500 M 0.01 M/0.1 M/1 M 1 mA @ 500 k
1000 V 20 M/200 M/1000 M 0.01 M/0.1 M/1 M 1 mA @ 1 M
Insulation pretest
Insulation safety pretest Requires to connect the Tester to L, N and PE.
Loop and line impedance (Z
I
)
Range Resolution
10  (Hi current m mode)/20 /200 /2000  1 m/ 0.01 / 0.1 /1
Prospective earth fault current, PSC test
Range Resolution
1000 A/10 kA (50 kA) 1 A/0.1 kA
Computation: Prospective Earth Fault Current (PEFC) or Prospective Short Circuit Current (PSC) determined by dividing measured mains
voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type Model 1662 Model 1663/1664 FC
AC
1
G
2
, S
3
A/F
4
, AC
1
, G
2
, S
3
A/F, AC, B/B+
5
, G, S
1
Responds to AC.
2
General, no delay.
3
Time delay.
4
Responds to pulsed signal.
5
Responds to smooth DC signal.
RCD trip time test (ΔT)
Current Settings
1
Multiplier
Measurement Range
RCD Type G RCD Type S
10-30-100-300-500-1000 mA VAR x ½, x 1 310 ms 510 ms
10-30-100 mA x 5 50 ms 160 ms
1
1000 mA type AC only. 700 mA maximum type A in VAR mode, VAR mode not available for type B.
RCD trip current measurement/ramp test (I
ΔN
)
Current Range Step Size
Dwell Time
Measurement AccuracyType G Type S
30 % to 110 % of RCD rated current
1
10 % of I
N
2
300 ms/step 500 ms/step ± 5 %
Notes
30 % to 210 % for Type A I
N
= 10mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
1
30 % to 150 % for Type A I
N
> 10 mA.
2
5 % for Type B
Earth resistance test (RE) Model 1664 FC and 1663 only
Range Resolution Frequency Output Voltage
200 /2000  0.1/1 128 Hz 25 V
Phase sequence indicaton
Icon Range Display
Phase Sequence indicator is active 100 to 500 V “1-2-3”: or “3-2-1”
5 Fluke Corporation 1660 Series Multifunction Installation Testers
Included Accessories
6x AA (IEC LR6) cell batteries,
C1600 hard carrying case, zero
adapter, heavy duty mains cord,
STD standard test lead set,
padded carrying and waist strap,
quick reference guide, TP165X
remote control probe and lead set
(FTP/UK fused probes, UK only),
User’s manual on CD-ROM
Ordering Information
Fluke 1664 FC Multifunction
Installation Tester with Auto Test,
Insulation PreTest, Fluke
Connect
®
compatibility
Fluke 1663 Multifunction
Installation Tester
Fluke 1662 Multifunction
Installation Tester
All trademarks are the property of their respective owners. WiFi or cellular service required to share
data. Smartphone, wireless service and data plan not included with purchase. First 5 GB of storage is
free. Phone support details can be viewed at fluke.com/phones.
Smartphone wireless service and data plan not included with purchase.
Fluke Connect
®
is not available in all countries.
Preventive maintenance simplified. Rework eliminated.
Save time and improve the reliability of your maintenance data by
wirelessly syncing measurements using the Fluke Connect
®
system.
Eliminate data-entry errors by saving measurements directly from the
tool and associating them with the work order, report or asset record.
Maximize uptime and make confident maintenance decisions with data
you can trust and trace.
Access baseline, historical and current measurements by asset.
Move away from clipboards, notebooks and multiple spreadsheets with
a wireless one-step measurement transfer.
Share your measurement data using ShareLive
video calls and emails.
Fluke 1664 FC is part of a growing system of connected test tools
and equipment maintenance software. Visit the website to learn more
about the Fluke Connect
®
system.
Find out more at flukeconnect.com
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
Fluke. Keeping your world up and running.
®
.
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0)40 267 5100 or
Fax +31 (0)40 267 5222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2016 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 4/2016 6004616a-en
Modification of this document is not
permitted without written permission
from Fluke Corporation.

FLK-1663 UK

Mfr. #:
Manufacturer:
Description:
UKAS(1135130) 1663 TESTER UK VERSION, EA
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet