1Description
Output loop-powered 2-way isolator
MINI MCR-2-UI-I-OLP(-PT)(-C)
© PHOENIX CONTACT
Data sheet
The 2-way output loop-powered isolator with plug-in
connection technology, which can be configured using DIP
switches, is used for the electrical isolation, conversion, and
filtering of unipolar and bipolar standard and normalized
signals.
The device allows operation on an active analog input
module.
The device is powered via the current loop of the controller.
On the input side, standard analog signals and non-
standard analog signals can be connected, ranging from
2mA or 50mV up to 40mA or 30V. These are converted to
a 4mA...20mA signal.
There is no need for adjustment following a measuring
range changeover.
Features
Output loop-powered 2-way isolator with plug-in
connection technology
Approval for Ex-zone 2 (nA)
74 input ranges can be set via DIP switches
Screw or push-in connection available
Reinforced insulation according to IEC 61010-1
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
This device offers the option of NFC communication.
You can use the MINI Analog Pro Smartphone app to call-up DIP switch setting help and comprehensive
module information via the NFC interface of your Smartphone.
The MINI Analog Pro Smartphone app is available to you free.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products
.
This document is valid for the products listed in the “Ordering data”.
106298_en_02
2016-02-29
MINI MCR-2-UI-I-OLP(-PT)(-C)
106298_en_02 PHOENIX CONTACT 2 / 12
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 5
5 Safety regulations and installation notes.................................................................................. 8
5.1 Installation notes ................................................................................................................. 8
5.2 Installation in Zone 2............................................................................................................. 8
5.3 UL Notes ........................................................................................................................... 8
6 Installation ............................................................................................................................... 9
6.1 Connection notes ................................................................................................................ 9
6.2 Structure ........................................................................................................................... 9
6.3 Block diagram..................................................................................................................... 9
6.4 Power supply...................................................................................................................... 9
6.5 Assembly........................................................................................................................... 9
6.6 FASTCON Pro plugs .......................................................................................................... 10
6.7 Current measurement ......................................................................................................... 10
6.8 Marking........................................................................................................................... 10
7 Configuration ......................................................................................................................... 11
8 Status indicator...................................................................................................................... 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
106298_en_02 PHOENIX CONTACT 3 / 12
Description Ty pe Order No. Pcs./Pkt.
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Screw connection technology, standard
configuration.
MINI MCR-2-UI-I-OLP 2902061 1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Push-in connection technology, standard
configuration.
MINI MCR-2-UI-I-OLP-PT 2902063 1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Screw connection technology, order
configuration.
MINI MCR-2-UI-I-OLP-C 2902060 1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Push-in connection technology, order
configuration.
MINI MCR-2-UI-I-OLP-PT-C 2902062 1
3Ordering data
Accessories Ty pe Order No. Pcs./Pkt.
Marker for end clamp, Sheet, white, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5) 0801505 10
Marker for end clamp, can be ordered: by sheet, white, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) CUS 0801589 1
Marker for end clamp, Sheet, yellow, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5) YE 0830340 10
Marker for end clamp, can be ordered: by sheet, yellow, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) YE CUS 0830348 1
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) 0819301 10
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L 0820138 5
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) YE 0822615 10
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) CUS 0824550 1
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) YE CUS 0824551 1
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L CUS 0824552 1
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L YE 0825325 5
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L YE CUS 0826680 1

2902061

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules MINI MCR-2-UI-I-OLP
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union