https://www.phoenixcontact.com/us/products/2839059
12/4/13Page2/5
Surge protection device-C7/16-LAMBDA/4-2.0-BB-SET-2839059
Technical data
General
Color nickel
Mounting type Connection-specific intermediate plugging
Design Attachment plug
Direction of action Line-Shield/Earth Ground
Protective circuit
IEC test classification C2
C3
D1
VDE requirement class C2
C3
D1
Nominal current I
N
5 A (25 °C)
Nominal discharge current I
n
(8/20) µs (Core-Earth)
20 kA
Nominal discharge current I
n
(8/20) µs (Core-Shield)
20 kA
Total surge current (8/20) µs 20 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 10 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike ≤ 10 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 10 V
Output voltage limitation at 1 kV/µs (Core-Shield) static ≤ 10 V
Residual voltage at I
n
, (conductor-ground)
≤ 20 V
Residual voltage at In, (conductor-shield) ≤ 20 V
Voltage protection level U
P
(Core-Earth)
≤ 20 V
Input attenuation aE, asym. 0.3 dB (1.7 GHz ... 2.3 GHz)
Frequency range 1.7 GHz ... 2.3 GHz
Standing wave ratio SWR in a 50 Ω system ≤ 1.25 (1.7 GHz ... 2.3 GHz)
Permissible HF power P
max.
at SWR=xx (50 Ohm system)
≤ 400 W (VSWR = 1.2)
≤ 500 W (VSWR = 1.0)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C2 (10 kV/5 kA)
D1 (2.5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Shield) C2 (10 kV/5 kA)
D1 (2.5 kA)
Connection data
Connection method 7/16 connector
Connection type IN 7/16 connector, female
Connection type OUT 7/16 connector, female
Standards and Regulations