2813512

https://www.phoenixcontact.com/pi/products/2813512
08/19/2018Page1/5
Signal conditioner-MINI MCR-SL-U-I-0-2813512
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 0
V ... 10 V, output signal: 0 mA ... 20 mA
Product Description
The 6.2mm wide standard signal 3-way isolating amplifier MINI MCR-SL-U-I-... is used for electrical isolation, conversion, amplification and filtering
of standard signals.
On the input side, 0...10 V are measured, and made available at the module output as a galvanically isolated 0...20 mA, or 4...20 mA signal.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.
Why buy this product
Power supply possible via the foot element (TBUS)
Low power consumption
Entry-level alternative to configurable signal conditioners
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
3-way isolation
Fixed signal combinations
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356100656
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 6.2 mm
Height 93.1 mm
https://www.phoenixcontact.com/pi/products/2813512
08/19/2018Page2/5
Signal conditioner-MINI MCR-SL-U-I-0-2813512
Technical data
Dimensions
Depth 102.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Input data
Number of inputs 1
Configurable/programmable no
Voltage input signal 0 V ... 10 V
max. input voltage 30 V
Input resistance of voltage input approx. 100 kΩ
Output data
Number of outputs 1
Configurable/programmable no
Current output signal 0 mA ... 20 mA
Max. output current 28 mA
Load/output load current output ≤ 500 Ω
Ripple
< 20 mV
PP
(at 500 Ω)
Power supply
Nominal supply voltage 24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Max. current consumption < 28 mA
Power consumption < 600 mW
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Stripping length 12 mm
Screw thread M3
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
https://www.phoenixcontact.com/pi/products/2813512
08/19/2018Page3/5
Signal conditioner-MINI MCR-SL-U-I-0-2813512
Technical data
General
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Limit frequency (3 dB) approx. 100 Hz
Step response (10-90%) approx. 3.5 ms
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 30 V AC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
GL GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 5 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 5 %
Designation Conducted interferences
Standards/regulations EN61000-4-6
Typical deviation from the measuring range final value 5 %
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL

2813512

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules MINI MCR-SL-U-I-0
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union