https://www.phoenixcontact.com/pi/products/2813512
08/19/2018Page3/5
Signal conditioner-MINI MCR-SL-U-I-0-2813512
Technical data
General
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Limit frequency (3 dB) approx. 100 Hz
Step response (10-90%) approx. 3.5 ms
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 30 V AC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
GL GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 5 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 5 %
Designation Conducted interferences
Standards/regulations EN61000-4-6
Typical deviation from the measuring range final value 5 %
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL