MODEL FCA200F-24
MAX OUTPUT WATTAGE[W] 200
(
Peak 1
,
008
)
DC OUTPUT 24V 8.4
(
Peak 42
)
A
SPECIFICATIONS
MODEL FCA200F-24
INPUT
VOLTAGE[V] AC187 - 528 1
f
or DC265 - 530
CURRENT[A]
ACIN 240V
1.10typ
ACIN 480V
0.55typ
FREQUENCY[Hz] 50/60
(
47-63
)
EFFICIENCY[%]
ACIN 240V
81typ
ACIN 480V
81typ
POWER FACTOR
ACIN 240V
0.98typ
ACIN 480V
0.93typ
INRUSH CURRENT[A]
ACIN 240V
25typ
(
At cold start
)(
At Room Temperature
)
ACIN 480V
50typ
(
At cold start
)(
At Room Temperature
)
LEAKAGE CURRENT[mA] 1.5max
(
60Hz
,
According to IEC60950
)
OUTPUT
VOLTAGE[V] 24
CURRENT[A]
*
1
8.4
(
Peak 42
)
LINE REGULATION[mV] 96max
LOAD REGULATION[mV]
0 - 8.4A
150max
RIPPLE[mVp-p]
0to+50
C
*
2
240max
-10-0
C
*
2
320max
RIPPLE NOISE[mVp-p]
0to+50
C
*
2
680max
-10-0
C
*
2
720max
TEMPERATURE REGULATION[mV]
-10 to +50
C
600max
DRIFT[mV]
*
5
100max
START-UP TIME[ms] 800max
(
ACIN 240V
,
Io=100%
)
HOLD-UP TIME[ms] 100typ
(
ACIN 240V
,
Io=100%
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
21.6 - 26.4
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of peak current and recovers automatically
OVERVOLTAGE PROTECTION
Works at 115 - 140% of rating
OPERATING INDICATION LED
(
Green
)
ISOLATION
INPUT-OUTPUT AC3
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
INPUT-FG AC2
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
OUTPUT-FG AC500V 1minute
,
Cutoff current = 100mA
,
DC500V 50M
W
min
(
At Room Temperature
)
ENVIRONMENT
OPERATING TEMP.
,
HUMID.AND ALTITUDE
-10 to +60
C
,
20 - 90%RH
(
Non condensing
)(
Refer to DERATING CURVE
),
3
,
000m
(
10
,
000feet
)
max
STORAGE TEMP.
,
HUMID.AND ALTITUDE
-20 to +75
C
,
20 - 90%RH
(
Non condensing
),
9
,
000m
(
30
,
000feet
)
max
VIBRATION
*
3
10 - 55Hz
,
19.6m/s
2
(
2G
),
3minutes period
,
60minutes each along X
,
Y and Z axis
IMPACT
*
3
196.1m/s
2
(
20G
),
11ms
,
once each X
,
Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS UL60950-1
,
C-UL
,
EN60950-1
CONDUCTED NOISE Complies with FCC-A
,
CISPR11-A
,
EN55011-A
OTHERS
CASE SIZE/WEIGHT
*
4
150
X
125
X
125mm
(
W
X
H
X
D
)
/1
,
700g max
COOLING METHOD Convection
*1 Peak current for 50ms in a 30seconds period is acceptable.
*2 In case of rated input/output(ACIN240-480v/8.4A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used.
*3 Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual).
*4 Depth of power supply is 133mm with DIN rail attachment.
*5 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*6 Please contact us about safety approvals for the model with option.
FCA200F
AC-DC Power Supplies Enclosed type
FCA 200 F -24 -O
Ordering information
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional
*6
N1
:with DIN rail attach-
ment
12345
FCA
FCA-6