FCA75F-24-CN1

MODEL FCA50F-24
MAX OUTPUT WATTAGE[W] 50
(
Peak 160
)
DC OUTPUT 24V 2.1
(
Peak 6.7
)
A
SPECIFICATIONS
MODEL FCA50F-24
INPUT
VOLTAGE[V] AC187 - 528 1
f
or DC265 - 746
CURRENT[A]
ACIN 240V
0.55typ
ACIN 480V
0.30typ
FREQUENCY[Hz] 50/60
(
47-63
)
EFFICIENCY[%]
ACIN 240V
82typ
ACIN 480V
78typ
INRUSH CURRENT[A]
ACIN 240V
25typ
(
At cold start
)(
At Room Temperature
)
ACIN 480V
50typ
(
At cold start
)(
At Room Temperature
)
LEAKAGE CURRENT[mA] 0.75max
(
60Hz
,
According to IEC60950
)
OUTPUT
VOLTAGE[V] 24
CURRENT[A]
*
1
2.1
(
Peak 6.7
)
LINE REGULATION[mV] 96max
LOAD REGULATION[mV]
0 - 2.1A
150max
0 - 6.7A
480max
RIPPLE[mVp-p]
0to+50
C
*
2
240max
-10-0
C
*
2
320max
RIPPLE NOISE[mVp-p]
0to+50
C
*
2
680max
-10-0
C
*
2
720max
TEMPERATURE REGULATION[mV]
-10 to +50
C
600max
DRIFT[mV]
*
5
100max
START-UP TIME[ms] 800max
(
ACIN 240V
,
Io=100%
)
HOLD-UP TIME[ms] 10typ
(
ACIN 240V
,
Io=100%
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
21.6 - 26.4
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of peak current and recovers automatically
OVERVOLTAGE PROTECTION
Works at 115 - 140% of rating
OPERATING INDICATION LED
(
Green
)
ISOLATION
INPUT-OUTPUT AC3
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
INPUT-FG AC2
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
OUTPUT-FG AC500V 1minute
,
Cutoff current = 100mA
,
DC500V 50M
W
min
(
At Room Temperature
)
ENVIRONMENT
OPERATING TEMP.
,
HUMID.AND ALTITUDE
-10 to +70
C
,
20 - 90%RH
(
Non condensing
)(
Refer to DERATING CURVE
),
3
,
000m
(
10
,
000feet
)
max
STORAGE TEMP.
,
HUMID.AND ALTITUDE
-20 to +75
C
,
20 - 90%RH
(
Non condensing
),
9
,
000m
(
30
,
000feet
)
max
VIBRATION
*
3
10 - 55Hz
,
19.6m/s
2
(
2G
),
3minutes period
,
60minutes each along X
,
Y and Z axis
IMPACT
*
3
196.1m/s
2
(
20G
),
11ms
,
once each X
,
Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS UL60950-1
,
C-UL
,
EN60950-1
CONDUCTED NOISE Complies with FCC-A
,
CISPR11-A
,
EN55011-A
OTHERS
CASE SIZE/WEIGHT
*
4
50
X
125
X
124mm
(
W
X
H
X
D
)
/ 640g max
COOLING METHOD Convection
*1 Peak current for 150ms in a 30seconds period is acceptable.
*2 In case of rated input/output(ACIN240-480v/2.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used.
*3 Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual).
*4 Depth of power supply is 132mm with DIN rail attachment.
*5 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*6 Please contact us about safety approvals for the model with option.
FCA50F
AC-DC Power Supplies Enclosed type
FCA 50 F -24 -O
Ordering information
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional
*6
N1
:with DIN rail attach-
ment
R
12345
FCA
FCA-2
¡
RISE TIME & FALL TIME
¡
STATIC CHARACTERISTICS
OUTPUT VOLTAGE V
OUTPUT VOLTAGE V
RIPPLE mVp-p
INPUT VOLTAGE
V 60Hz
¡
INRUSH CURRENT
¡
OVERCURRENT CHARACTERISTICS
OUTPUT CURRENT
A
Io=100%
Ripple
Output Voltage
(AC 100V)
Io=100%
Io=50%
DC Output
AC Input
ACIN 480V
50ms/DIV
OUTPUT VOLTAGE V
50ms/DIV
20A/DIV
Input Voltage AC480V
60Hz
100%
Input voltage AC480V
Frequency
Load
150 160 170 180 190 200 210 220 230 240 250
24
22
20
18
16
14
12
10
8
25
50
75
100
25
20
15
10
5
0
26
24
22
20
18
16
14
12
24681012
FCA
FCA-3
FCA50F
External view
Terminal
Block
(M4)
+V
-V
FG
AC(L)
AC(N)
+
-
FG
AC(L)
AC(N)
FCA50F-24
(
22
)
(
12
)
(
7
)
(
116
)
(
72
)
(
35.5
)
(
8
)
(
110
)
(
102
)
(
34
)
(
24.5
)
(
15.5
)
(
11.5
)
13max
13 10
124
125
LED
Voltage Adjust
7
16
50
30
Spacer
FCA50F-24-N1 only
FCA50F-24-N1 only
DIN Rail Attachment
71.1
±
0.5
25.4
±
0.5
45.9
18max
50
44.5
25.4
Terminal Block Cover
119
º
3.8
3-M3 Mounting Hole
12.7
Weight : 640g or less
Tolerance : ±1
Mounting torque : 0.6Nm
(6.3kgfcm)max
Dimensions in mm.
Performance data
MODEL FCA75F-24
MAX OUTPUT WATTAGE[W] 75
(
Peak 240
)
DC OUTPUT 24V 3.1
(
Peak 10
)
A
SPECIFICATIONS
MODEL FCA75F-24
INPUT
VOLTAGE[V] AC187 - 528 1
f
or DC265 - 746
CURRENT[A]
ACIN 240V
0.80typ
ACIN 480V
0.45typ
FREQUENCY[Hz] 50/60
(
47-63
)
EFFICIENCY[%]
ACIN 240V
82typ
ACIN 480V
78typ
INRUSH CURRENT[A]
ACIN 240V
25typ
(
At cold start
)(
At Room Temperature
)
ACIN 480V
50typ
(
At cold start
)(
At Room Temperature
)
LEAKAGE CURRENT[mA] 0.75max
(
60Hz
,
According to IEC60950
)
OUTPUT
VOLTAGE[V] 24
CURRENT[A]
*
1
3.1
(
Peak 10
)
LINE REGULATION[mV] 96max
LOAD REGULATION[mV]
0 - 3.1A
150max
0 - 10A 480max
RIPPLE[mVp-p]
0to+50
C
*
2
240max
-10-0
C
*
2
320max
RIPPLE NOISE[mVp-p]
0to+50
C
*
2
680max
-10-0
C
*
2
720max
TEMPERATURE REGULATION[mV]
-10 to +50
C
600max
DRIFT[mV]
*
5
100max
START-UP TIME[ms] 800max
(
ACIN 240V
,
Io=100%
)
HOLD-UP TIME[ms] 10typ
(
ACIN 240V
,
Io=100%
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
21.6 - 26.4
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of peak current and recovers automatically
OVERVOLTAGE PROTECTION
Works at 115 - 140% of rating
OPERATING INDICATION LED
(
Green
)
ISOLATION
INPUT-OUTPUT AC3
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
INPUT-FG AC2
,
000V 1minute
,
Cutoff current = 10mA
,
DC500V 50M
W
min
(
At Room Temperature
)
OUTPUT-FG AC500V 1minute
,
Cutoff current = 100mA
,
DC500V 50M
W
min
(
At Room Temperature
)
ENVIRONMENT
OPERATING TEMP.
,
HUMID.AND ALTITUDE
-10 to +70
C
,
20 - 90%RH
(
Non condensing
)(
Refer to DERATING CURVE
),
3
,
000m
(
10
,
000feet
)
max
STORAGE TEMP.
,
HUMID.AND ALTITUDE
-20 to +75
C
,
20 - 90%RH
(
Non condensing
),
9
,
000m
(
30
,
000feet
)
max
VIBRATION
*
3
10 - 55Hz
,
19.6m/s
2
(
2G
),
3minutes period
,
60minutes each along X
,
Y and Z axis
IMPACT
*
3
196.1m/s
2
(
20G
),
11ms
,
once each X
,
Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS UL60950-1
,
C-UL
,
EN60950-1
CONDUCTED NOISE Complies with FCC-A
,
CISPR11-A
,
EN55011-A
OTHERS
CASE SIZE/WEIGHT
*
4
65
X
125
X
124mm
(
W
X
H
X
D
)
/ 750g max
COOLING METHOD Convection
*1 Peak current for 150ms in a 30seconds period is acceptable.
*2 In case of rated input/output(ACIN240-480v/3.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used.
*3 Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual).
*4 Depth of power supply is 132mm with DIN rail attachment.
*5 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*6 Please contact us about safety approvals for the model with option.
FCA75F
AC-DC Power Supplies Enclosed type
FCA 75 F -24 -O
Ordering information
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional
*6
N1
:with DIN rail attach-
ment
R
12345
FCA
FCA-4

FCA75F-24-CN1

Mfr. #:
Manufacturer:
Cosel
Description:
DIN Rail Power Supplies 187-528VAC 265-530DC 75W 24V 3.1A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union