Datasheet SHT1x
www.sensirion.com Version 5 – December 2011 4/12
following conditions: Temperature shall be in the range of
10°C 50°C (0 125°C for limited time) and humidity at
20 60%RH (sensors that are not stored in ESD bags).
For sensors that have been removed from the original
packaging we recommend to store them in ESD bags
made of metal-in PE-HD
8
.
In manufacturing and transport the sensors shall be
prevented of high concentration of chemical solvents and
long exposure times. Out-gassing of glues, adhesive tapes
and stickers or out-gassing packaging material such as
bubble foils, foams, etc. shall be avoided. Manufacturing
area shall be well ventilated.
For more detailed information please consult the
document “Handling Instructions” or contact Sensirion.
1.4 Reconditioning Procedure
As stated above extreme conditions or exposure to solvent
vapors may offset the sensor. The following reconditioning
procedure may bring the sensor back to calibration state:
Baking: 100 – 105°C at < 5%RH for 10h
Re-Hydration: 20 – 30°C at ~ 75%RH for 12h
9
.
1.5 Temperature Effects
Relative humidity reading strongly depends on
temperature. Therefore, it is essential to keep humidity
sensors at the same temperature as the air of which the
relative humidity is to be measured. In case of testing or
qualification the reference sensor and test sensor must
show equal temperature to allow for comparing humidity
readings.
If the SHT1x shares a PCB with electronic components
that produce heat it should be mounted in a way that
prevents heat transfer or keeps it as low as possible.
Measures to reduce heat transfer can be ventilation,
reduction of copper layers between the SHT1x and the
rest of the PCB or milling a slit into the PCB around the
sensor (see Figure 8).
Figure 8: Top view of example of mounted SHT1x with slits
milled into PCB to minimize heat transfer.
8
For example, 3M antistatic bag, product “1910” with zipper .
9
75%RH can conveniently be generated with saturated NaCl solution.
100 – 105°C correspond to 212 – 221°F, 20 – 30°C correspond to 68 – 86°F
Furthermore, there are self-heating effects in case the
measurement frequency is too high. Please refer to
Section 3.3 for detailed information.
1.6 Light
The SHT1x is not light sensitive. Prolonged direct
exposure to sunshine or strong UV radiation may age the
housing.
1.7 Membranes
SHT1x does not contain a membrane at the sensor
opening. However, a membrane may be added to prevent
dirt and droplets from entering the housing and to protect
the sensor. It will also reduce peak concentrations of
chemical vapors. For optimal response times the air
volume behind the membrane must be kept minimal.
Sensirion recommends and supplies the SF1 filter cap for
optimal IP54 protection (for higher protection i.e. IP67 -
SF1 must be sealed to the PCB with epoxy). Please
compare Figure 9.
Figure 9: Side view of SF1 filter cap mounted between PCB and
housing wall. Volume below membrane is kept minimal.
1.8 Materials Used for Sealing / Mounting
Many materials absorb humidity and will act as a buffer
increasing response times and hysteresis. Materials in the
vicinity of the sensor must therefore be carefully chosen.
Recommended materials are: Any metals, LCP, POM
(Delrin), PTFE (Teflon), PE, PEEK, PP, PB, PPS, PSU,
PVDF, PVF.
For sealing and gluing (use sparingly): Use high filled
epoxy for electronic packaging (e.g. glob top, underfill),
and Silicone. Out-gassing of these materials may also
contaminate the SHT1x (see Section 1.3). Therefore try to
add the sensor as a last manufacturing step to the
assembly, store the assembly well ventilated after
manufacturing or bake at >50°C for 24h to outgas
contaminants before packing.
1.9 Wiring Considerations and Signal Integrity
Carrying the SCK and DATA signal parallel and in close
proximity (e.g. in wires) for more than 10cm may result in
cross talk and loss of communication. This may be
A5Z
11
housing
PCB
o-ring
Melted plastic pin
SHT1x
membrane
Datasheet SHT1x
www.sensirion.com Version 5 – December 2011 5/12
resolved by routing VDD and/or GND between the two
data signals and/or using shielded cables. Furthermore,
slowing down SCK frequency will possibly improve signal
integrity. Power supply pins (VDD, GND) must be
decoupled with a 100nF capacitor if wires are used.
Capacitor should be placed as close to the sensor as
possible. Please see the Application Note “ESD, Latch-up
and EMC” for more information.
1.10 ESD (Electrostatic Discharge)
ESD immunity is qualified according to MIL STD 883E,
method 3015 (Human Body Model at ±2 kV).
Latch-up immunity is provided at a force current of
±100mA with T
amb
= 80°C according to JEDEC78A. See
Application Note “ESD, Latch-up and EMC” for more
information.
2 Interface Specifications
Pin
Name
Comment
1
GND
Ground
2
DATA
Serial Data, bidirectional
3
SCK
Serial Clock, input only
4
VDD
Source Voltage
NC
NC
Must be left unconnected
Table 1: SHT1x pin assignment, NC remain floating.
2.1 Power Pins (VDD, GND)
The supply voltage of SHT1x must be in the range of 2.4 –
5.5V, recommended supply voltage is 3.3V. Power supply
pins Supply Voltage (VDD) and Ground (GND) must be
decoupled with a 100 nF capacitor – see Figure 10.
The serial interface of the SHT1x is optimized for sensor
readout and effective power consumption. The sensor
cannot be addressed by I
2
C protocol; however, the sensor
can be connected to an I
2
C bus without interference with
other devices connected to the bus. The controller must
switch between the protocols.
Figure 10: Typical application circuit, including pull up resistor
R
P
and decoupling of VDD and GND by a capacitor.
2.2 Serial clock input (SCK)
SCK is used to synchronize the communication between
microcontroller and SHT1x. Since the interface consists of
fully static logic there is no minimum SCK frequency.
2.3 Serial data (DATA)
The DATA tri-state pin is used to transfer data in and out
of the sensor. For sending a command to the sensor,
DATA is valid on the rising edge of the serial clock (SCK)
and must remain stable while SCK is high. After the falling
edge of SCK the DATA value may be changed. For safe
communication DATA valid shall be extended T
SU
and T
HO
before the rising and after the falling edge of SCK,
respectively see Figure 11. For reading data from the
sensor, DATA is valid T
V
after SCK has gone low and
remains valid until the next falling edge of SCK.
To avoid signal contention the microcontroller must only
drive DATA low. An external pull-up resistor (e.g. 10kΩ) is
required to pull the signal high it should be noted that
pull-up resistors may be included in I/O circuits of
microcontrollers. See Table 2 for detailed I/O characteristic
of the sensor.
2.4 Electrical Characteristics
The electrical characteristics such as power consumption,
low and high level input and output voltages depend on
the supply voltage. Table 2 gives electrical characteristics
of SHT1x with the assumption of 5V supply voltage if not
stated otherwise.
Parameter
Conditions
min
typ
max
Units
Power supply DC
10
2.4
3.3
5.5
V
Supply current
measuring
0.55
1
mA
average
11
2
28
µ
A
sleep
0.3
1.5
µ
A
Low level output
voltage
I
OL
< 4 mA 0 250 mV
High
level output
voltage
R
P
< 25 kΩ 90%
100%
VDD
Low level input
voltage
Negative going
0% 20%
VDD
High level input
voltage
Positive going 80%
100%
VDD
Input current
on
pads
1
µ
A
Output current
on
4
mA
Tri
-
stated (off)
10
20
µ
A
Table 2: SHT1x DC characteristics. R
P
stands for pull up
resistor, while I
OL
is low level output current.
10
Recommended voltage supply for highest accuracy is 3.3V, due to sensor
calibration.
11
Minimum value with one measurement of 8bit resolution without OTP reload
per second. Typical value with one measurement of 12bit resolution per
second.
A5Z
11
NC
NC
NC
NC
NC
NC
1
2
3
4
Micro-
Controller
(Master)
GND
2.4 – 5.5V
DATA
SCK
VDD
R
P
VDD
GND
SHT1x
(Slave)
A5Z
11
100nF
10
k
Datasheet SHT1x
www.sensirion.com Version 5 – December 2011 6/12
Absolute maximum ratings for VDD versus GND are +7V
and -0.3V.
Exposure to absolute maximum rating
conditions for extended periods may affect the sensor
reliability (e.g. hot carrier degradation, oxide breakdown).
For proper communication with the sensor it is essential to
make sure that signal design is strictly within the limits
given in Table 3 and Figure 11.
Figure 11: Timing Diagram, abbreviations are explained in
Table 3. Bold DATA line is controlled by the sensor, plain DATA
line is controlled by the micro-controller. Note that DATA valid
read time is triggered by falling edge of anterior toggle.
Parameter Conditions min typ max
Units
F
SCK
SCK Frequency
VDD > 4.5V
0 0.1 5 MHz
VDD < 4.5V
0 0.1 1 MHz
T
SCKx
SCK hi/low time 100
ns
T
R
/T
F
SCK rise/fall time 1 200
* ns
T
FO
DATA fall time
OL = 5pF 3.5 10 20 ns
OL = 100pF
30 40 200
ns
T
RO
DATA rise time ** ** ** ns
T
V
DATA valid time 200
250
*** ns
T
SU
DATA setup time 100
150
*** ns
T
HO
DATA hold time 10 15 **** ns
*
T
R_max
+ T
F_max
= (F
SCK
)
-1
T
SCKH
T
SCKL
**
T
R0
is determined by the R
P
*C
bus
time
-
constant at DATA
line
***
T
V_max
and T
SU_max
depend on external pull
-
up resistor (R
P
) and total bus
line capacitance (Cbus) at DATA line
****
T
H0_max
< T
V
max (T
R0
, T
F0
)
Table 3: SHT1x I/O signal characteristics, OL stands for Output
Load, entities are displayed in Figure 11.
3 Communication with Sensor
3.1 Start up Sensor
As a first step the sensor is powered up to chosen supply
voltage VDD. The slew rate during power up shall not fall
below 1V/ms. After power-up the sensor needs 11ms to
get to Sleep State. No commands must be sent before
that time.
3.2 Sending a Command
To initiate a transmission, a Transmission Start sequence
has to be issued. It consists of a lowering of the DATA line
while SCK is high, followed by a low pulse on SCK and
raising DATA again while SCK is still high – see Figure 12.
Figure 12: "Transmission Start" sequence
The subsequent command consists of three address bits
(only ‘000’ is supported) and five command bits. The
SHT1x indicates the proper reception of a command by
pulling the DATA pin low (ACK bit) after the falling edge of
the 8th SCK clock. The DATA line is released (and goes
high) after the falling edge of the 9th SCK clock.
Command
Code
Reserved
0000x
Measure T
emperature
00011
Measure Relative Humidity
00101
Read Status Register
00111
Write Status Register
00110
Reserved
0101x
-
1110x
Soft reset,
resets the interface, clears the
status register to default values. Wait minimum
11 ms before next command
11110
Table 4: SHT1x list of commands
3.3 Measurement of RH and T
After issuing a measurement command (‘00000101’ for
relative humidity, ‘00000011’ for temperature) the
controller has to wait for the measurement to complete.
This takes a maximum of 20/80/320 ms for a 8/12/14bit
measurement. The time varies with the speed of the
internal oscillator and can be lower by up to 30%. To
signal the completion of a measurement, the SHT1x pulls
data line low and enters Idle Mode. The controller must
wait for this Data Ready signal before restarting SCK to
readout the data. Measurement data is stored until
readout, therefore the controller can continue with other
tasks and readout at its convenience.
Two bytes of measurement data and one byte of CRC
checksum (optional) will then be transmitted. The micro
controller must acknowledge each byte by pulling the
DATA line low. All values are MSB first, right justified (e.g.
the 5
th
SCK is MSB for a 12bit value, for a 8bit result the
first byte is not used).
DATA valid read
DATA valid write
DATA
SCK
80%
2
0%
80%
2
0%
T
V
T
SCKL
T
SU
T
HO
T
SCK
T
SCKH
T
R
T
F
T
RO
T
FO
DATA
SCK
80%
2
0%
80%
2
0%

SHT15

Mfr. #:
Manufacturer:
Sensirion
Description:
Board Mount Humidity Sensors Humid & Temp Sensor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet