https://www.phoenixcontact.com/pi/products/2903659
05/02/2017Page2/5
Single relay-REL-IR2/LDP- 12DC/2X21-2903659
Technical data
Coil side
Power dissipation for nominal condition 0.94 W
Contact side
Contact type 2 PDT
Type of switch contact Single contact
Contact material AgNi
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (At 24 mA)
Min. switching current 5 mA (at 24 V)
Maximum inrush current 30 A (20 ms, N/O contact)
Limiting continuous current 12 A
Interrupting rating (ohmic load) max. 288 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
3000 VA (for 250 V AC)
Switching capacity min. 0.12 W
Switching capacity in acc. with DIN VDE 0660/IEC 60947 2 A (at 24 V, DC13)
0.22 A (at 120 V, DC13)
0.11 A (at 250 V, DC13)
3 A (at 120 V, AC15)
1.5 A (at 240 V, AC15)
General
Test voltage relay winding/relay contact
2.5 kV
rms
(50 Hz, 1 min.)
Test voltage relay contact/relay contact
2.5 kV
rms
(50 Hz, 1 min.)
Test voltage PDT/PDT
2.5 kV
rms
(50 Hz, 1 min.)
Operating mode 100% operating factor
Degree of protection RT I
Mechanical service life
Approx. 2x 10
7
cycles
Mounting position any
Standards and Regulations
Connection in acc. with standard CSA
Standards/regulations IEC60664
IEC 61810
Rated insulation voltage 250 V AC
Rated surge voltage 4 kV
Insulation Basic insulation
Degree of pollution 3
Overvoltage category III