https://www.phoenixcontact.com/us/products/2859913
12/4/13Page2/5
Type 1 surge protection plug-FLT-CP-PLUS-350-ST-2859913
Technical data
Protective circuit
IEC test classification I
T1
EN type T1
Lightning protection class III-IV /50 kA (TT, TN-C-S)
Nominal voltage U
N
240 V AC
Maximum continuous operating voltage U
C
350 V AC
U
T
(TOV-proof)
415 V (5 s)
Nominal frequency f
N
50 Hz (60 Hz)
Standby power consumption P
C
≤ 2 mVA
Nominal discharge current I
n
(8/20) µs
25 kA
Impulse discharge current (10/350) µs, charge 12.5 As
Impulse discharge current (10/350) µs, specific energy 160.00 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
imp
25 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 1.5 kV
Voltage protection level U
p
≤ 1.5 kV
Response time ≤ 100 ns
Max. required backup fuse with branch wiring 315 A (gL/gG)
Max. required backup fuse with V-type through wiring 125 A (gL/gG)
Recommended backup fuse maximum 160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance I
P
with max. backup fuse (effective)
50 kA
Follow current quenching capacity If 50 kA (264 V AC)
25 kA (350 V AC)
Connection, protective circuit
Connection type IN FLASHTRAB/VALVETRAB plug-in system
Connection type OUT FLASHTRAB/VALVETRAB plug-in system
Standards and Regulations
Standards/regulations IEC 61643-1 2005
EN 61643-11 2002
EN 61643-11/A11 2007
UL 1449 ed. 2
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27140201