1Description
PLC-OS… relay modules, which can be used universally,
comprise 6.2 mm basic terminal blocks and plug-in
miniature solid-state relays with screw or spring-cage
connection.
1.1 Input Voltages From 24 V to 230 V
The PLC-OS… is available on the control side in all common
industrial voltages from 24 V to 230 V. A further advantage
is the ready-integrated input circuit. It consists of a status
indicator and polarity reversal protection function, and
ensures that the operating state is displayed clearly, also
preventing destruction of the optical electronics should the
polarity be accidentally reversed.
1.2 Plug-In Bridges Save Wiring
The PLC INTERFACE module achieves maximum
efficiency with the user-friendly FBST plug-in bridge system.
The PLC-OS… makes effective use of the bridging options
for the A1/A2 connection on the control side and for the
power supply at connection 13 on the load side. Especially
effective here are the 500 mm long color-insulated
continuous plug-in bridges that can easily be cut to the
required length and quickly inserted in the bridge shafts.
They eliminate the need for complicated and time-
consuming loop bridges.
1.3 Additional Advantages
Switching power of up to 24 V DC/3 A, depending on
the type
IP67-protected fully encapsulated optical electronics
Available with input or power solid-state relays as an
option
Integrated input circuit
Solid-state relay can be replaced using an engagement
lever
Wear-resistant switching
Resistant to vibrations and shocks
Inflammability class V0 according to UL94
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com
.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
PLC INTERFACE With Solid-State Relay,
Universal Version
PLC-OS…
103148_en_02 PHOENIX CONTACT 2
2Ordering Data
PLC INTERFACE With Screw Connection
Description Type Order No. Pcs./Pck.
PLC INTERFACE With Input Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC... basic
terminal block and plug-in miniature solid-state
relay (see INTERFACE catalog), for mounting on
3. Other input voltages on request.
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
1
PLCOSC- 24DC/48DC/100
PLCOSC-120UC/48DC/100
PLCOSC-230UC/48DC/100
2966728
2966744
2966757
10
10
10
PLC INTERFACE With Power Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC.../21
basic terminal block and plug-in miniature solid-
state relay (see INTERFACE catalog), for
mounting on
3. Other input voltages on
request.
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
1
PLCOSC- 24DC/24DC/2
PLCOSC-120UC/24DC/2
PLCOSC-230UC/24DC/2
2966634
2966650
2966663
10
10
10
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
PLC INTERFACE With Spring-Cage Connection
Description Type Order No. Pcs./Pck.
PLC INTERFACE With Input Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC... basic
terminal block and plug-in miniature solid-state
relay (see INTERFACE catalog), for mounting on
3. Other input voltages on request.
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
1
PLCOSP- 24DC/48DC/100
PLCOSP-120UC/48DC/100
PLCOSP-230UC/48DC/100
2967549
2967552
2967565
10
10
10
PLC INTERFACE With Power Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC.../21
basic terminal block and plug-in miniature solid-
state relay (see INTERFACE catalog), for
mounting on
3. Other input voltages on
request.
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
1
PLCOSP- 24DC/24DC/2
PLCOSP-120UC/24DC/2
PLCOSP-230UC/24DC/2
2967471
2967484
2967497
10
10
10
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
With the 120 V and 230 V modules, an OPT-60DC/... 60 V solid-state relay is normally used due to the input circuit integrated in the basic terminal
block.
For the protection of input and output, inductive loads must be dampened with an effective protective circuit.
Accessories
Description Type Order No. Pcs./Pck.
Insulating plate PLC-ATP BK 2966841 25
For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com.
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for
potential bridging) and for safe isolation between adjacent modules.
PLC-OS…
103148_en_02 PHOENIX CONTACT 3
3 Technical Data
Input Data PLCOS...48DC/100 PLCOS...24DC/2
Nominal input voltage
1
24 V DC 120 V AC/110 V DC
230 V AC/220 V DC
24 V DC 120 V AC/110 V DC
230 V AC/220 V DC
Permissible range (with reference to U
N
) 0.8 ... 1.2 x U
N
0.8 ... 1.1 x U
N
0.8 ... 1.2 x U
N
0.8 ... 1.1 x U
N
Switching level
1 signal ("H")
0 signal ("L")
0.8 x U
N
0.4 x U
N
0.8 x U
N
0.3 x U
N
0.8 x U
N
0.4 x U
N
0.8 x U
N
0.25 x U
N
Typical input current at U
N
8 mA 4 mA 9 mA 4 mA
Typical response time at U
N
20 μs6 ms20 μs6 ms
Typical release time at U
N
300 μs 10 ms 300 μs 10 ms
Transmission frequency f
limit
300 Hz 10 Hz 300 Hz 10 Hz
Input circuit Yellow LED,
protection
against polarity
reversal, free-
wheeling diode
Yellow LED, bridge
rectifier
Yellow LED,
protection
against polarity
reversal, free-
wheeling diode
Yellow LED, bridge
rectifier
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
Output Data PLCOS...48DC/100 PLCOS...24DC/2
Maximum switching voltage 48 V DC 33 V DC
Minimum switching voltage 3 V DC
Limiting continuous current 100 mA 3 A (see "Derating Curve")
Maximum inrush current 15 A (10 ms)
Output configuration 2-wire floating
Output circuit Protection against polarity reversal, surge protection
Voltage drop at maximum limiting continuous current 1 V 200 mV
General Data
Impulse voltage withstand level 2.5 kV, 50 Hz, 1 min.
Ambient temperature range
Operation
Storage/transport
-25°C ... 60°C
-40°C ... 85°C
Nominal operating mode 100% operating factor
Inflammability class according to UL 94 (housing) V0
Standards/specifications
1
IEC 60664, IEC 60664 A, DIN VDE 0110 (basic insulation)
Pollution degree 2
Surge voltage category III
Mounting position Any
Mounting Can be aligned without spacing
Conductor cross-section
Solid, with screw connection
Stranded, with screw connection
Solid, with spring-cage connection
Stranded, with spring-cage connection
0.14 mm
2
... 2.5 mm
2
(26 - 14 AWG)
0.14 mm
2
... 1.5 mm
2
(26 - 14 AWG)
0.2 mm
2
... 2.5 mm
2
(24 - 14 AWG)
0.2 mm
2
... 1.5 mm
2
(24 - 14 AWG)
Stripping length
Screw connection
Spring-cage connection
10 mm
8 mm
Dimensions (W x H x D) 6.2 mm x 94 mm x 80 mm
Housing material Polyamide PA, green
1
The PLC-ATP BK insulating plate must be installed for safe isolation between adjacent modules (see "Accessories"). FBST 8-PLC... or FBST 500... is
then used for potential bridging.

2967552