2981062

PSR-...-24UC/ESL4/3X1/1X2/B
100515_en_04 PHOENIX CONTACT 7
7Safety notes
WARNING: Risk of electric shock
During operation, parts of electrical switching
devices carry hazardous voltages.
Before working on the switching device, dis-
connect the power.
Please observe the safety regulations of elec-
trical engineering and industrial safety and lia-
bility associations!
Disregarding these safety regulations may re-
sult in death, serious personal injury or dam-
age to equipment.
Startup, mounting, modifications, and up-
grades should only be carried out by a skilled
electrical engineer!
WARNING: Risk of automatic machine re-
start!
For emergency stop applications, the ma-
chine must be prevented from restarting auto-
matically by a higher-level control system.
Protective covers must not be removed when
operating electrical switching devices.
WARNING: Danger due to faulty devices!
The devices may be damaged following an er-
ror and correct operation can no longer be en-
sured.
In the event of an error, replace the device im-
mediately.
Repairs to the device, especially if the hous-
ing must be opened, may only be carried out
by the manufacturer or authorized persons.
Otherwise the warranty is invalidated.
NOTE: Risk of damage to equipment due
to incorrect installation
For reliable operation, the safety relay must
be installed in housing protected from dust
and humidity (IP54).
Carry out wiring according to the application.
Refer to the “Application examples” section
for this.
NOTE: Risk of damage to equipment due
to noise emissions
When operating relay modules the operator
must meet the requirements for noise emis-
sion for electrical and electronic equipment
(EN 61000-6-4) on the contact side and, if re-
quired, take appropriate measures.
PSR-...-24UC/ESL4/3X1/1X2/B
100515_en_04 PHOENIX CONTACT 8
8 Operating and indication elements
Figure 3 PSR-SCP-24UC/ESL4/3X1/1X2/B and PSR-SPP-24UC/ESL4/3X1/1X2/B
Key:
9Diagnostics
For the diagnostic description, please refer to the applica-
tion manual for PSR safety relays.
S11
S35
S12
S22
A2
42
34
23
24
41
33
13
14
24
23
34
42
PS
R-ES
L4
A1 S33 S34 S11
A2
S22
S35
S12
K2
K1
Pow
er
P
S
R
-S
P
P- 24U
C
/E
S
L4
/3X
1/1X
2/B
Order No.: 29 81 06 2
APPROVALS
Serial No.
13 23 33 41
14 24 34 42
41
33
13
14
3
42
34
23
24
41
33
13
14
PS
R
-S
C
P
- 24U
C
/ES
L4/3X1/1X2/B
Order No.: 29 81 05 9
APPROVALS
Serial No.
13 23 33 41
14 24 34 42
41
33
13
14
24
23
34
42
PS
R-ES
L4
A1 S33 S34 S11
A2
S22
S35
S12
K2
K
1
Pow
er
1
2
4
5
6
9
7
8
10
11
Designation Explanation
1 Metal lock for mounting on the DIN rail
2 COMBICON plug-in screw terminal blocks
3 COMBICON plug-in spring-cage terminal blocks
4 13/14, 23/24, 33/34 enabling current paths
5 41/42 signaling current path
6 LED status indicator, green - K2
7 LED status indicator, green - K1
8 LED status indicator, green - Power
9 A1, A2 - supply voltage connection
10 S33, S34, S35 - start circuit (activating circuit)
11 S11, S12, S22 input circuit
PSR-...-24UC/ESL4/3X1/1X2/B
100515_en_04 9
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
10 Application example
10.1 Two-channel light grid monitoring (cross-
circuit detection
via light grid)
Manual activation
Automatic activation with jumper at S33-S35
Suitable up to category4, PLe (ENISO13849-1),
SILCL3 (EN62061)
Figure 4 Two-channel light grid monitoring
10.2 Two-channel emergency stop circuit without
cross-circuit detection, with monitored reset
button
Manual activation
Automatic activation with jumper at S33-S35
Suitable up to category 3, PL d (ENISO 13849-1),
SILCL2 (EN62061)
Figure 5 Two-channel emergency stop circuit without
cross-circuit detection
10.3 Single-channel emergency stop monitoring
Manual activation
Automatic activation with jumper at S33-S35
Suitable up to category 1, PL c (ENISO 13849-1),
SILCL1 (EN62061)
Figure 6 Single-channel emergency stop circuit with
monitored reset button
10.4 Two-channel safety door monitoring without
cross-circuit detection, with monitored reset
button
Manual activation
Automatic activation with jumper at S33-S35
Suitable up to category 3, PL d (ENISO 13849-1),
SILCL2 (EN62061)
Figure 7 Two-channel safety door monitoring without
cross-circuit detection