Data Sheet ADF4156
Rev. E | Page 15 of 24
FUNCTION REGISTER, R3
With the control bits (Bits[2:0]) of Register R2 set to 011, the
on-chip function register is programmed. Figure 20 shows the
input data format for programming this register.
Counter Reset
DB3 is the counter reset bit for the ADF4156. When this bit is
set to 1, the synthesizer counters are held in reset. For normal
operation, this bit should be 0.
Charge-Pump Three-State
When programmed to 1, DB4 puts the charge pump into three-
state mode. This bit should be set to 0 for normal operation.
Power-Down
DB5 on the ADF4156 provides the programmable power-down
mode. Setting this bit to 1 performs a power-down. Setting this
bit to 0 returns the synthesizer to normal operation. While in
software power-down mode, the part retains all information in
its registers. Only when supplies are removed are the register
contents lost.
When a power-down is activated, the following events occur:
1. The synthesizer counters are forced to their load state
conditions.
2. The charge pump is forced into three-state mode.
3. The digital lock detect circuitry is reset.
4. The RF
IN
input is debiased.
5. The input register remains active and capable of loading
and latching data.
Phase Detector Polarity
DB6 in the ADF4156 sets the phase detector polarity. When the
VCO characteristics are positive, this bit should be set to 1.
When the characteristics are negative, DB6 should be set to 0.
Note that the cycle slip reduction function cannot be used if the
phase detector polarity is set to negative.
Lock Detect Precision (LDP)
When DB7 is programmed to 0, the digital lock detect is set
high when the phase error on 40 consecutive phase detector
cycles is less than 10 ns each. When this bit is programmed to 1,
40 consecutive phase detector cycles of less than 6 ns each must
occur before the digital lock detect is set.
Σ-Δ Reset
For most applications, DB14 should be programmed to 0. When
DB14 is programmed to 0, the Σ-Δ modulator is reset to its starting
point, or starting phase word, on every write to Register R0. This
has the effect of producing consistent spur levels.
If it is not required that the Σ-Δ modulator be reset on each
write to Register R0, DB14 should be set to 1.
DB31 DB30 DB29 DB28 DB27 DB26 DB25 DB24 DB23 DB22 DB21 DB20 DB19 DB18 DB17 DB16 DB15 DB14 DB13 DB12 DB11 DB10 DB9 DB8 DB7 DB6 DB5 DB4 DB3 DB2 DB1 DB0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 U12 0 0 0 0 0 0 U11 U10 U9 U8 U7 C3(0) C2(1) C1(1)
CONTROL
BITS
RESERVED RESERVED
LDP
Σ-Δ RESET
PD
POLARITY
PD
CP THREE-
STATE
COUNTER
RESET
U11 LDP
0 10ns
1 6ns
U10 PD POLARITY
0 NEGATIVE
1 POSITIVE
U9 POWER-DOWN
0 DISABLED
1 ENABLED
U8
CP
THREE-STATE
0 DISABLED
1 ENABLED
U7
COUNTER
RESET
0 DISABLED
1 ENABLED
05863-014
U12 Σ-Δ RESET
0 ENABLED
1 DISABLED
Figure 20. Function Register (R3) Map
ADF4156 Data Sheet
Rev. E | Page 16 of 24
CLK DIV REGISTER, R4
With the control bits (Bits[2:0]) of Register R3 set to 100, the
on-chip clock divider register (R4) is programmed. Figure 21
shows the input data format for programming this register.
12-Bit Clock Divider Value
The 12-bit clock divider value sets the timeout counter for
activation of the fast-lock mode or a phase resync. See the Phase
Resync section for more information.
Clock Divider Mode
DB[20:19] control the mode of the clock divider in the ADF4156.
These bits should be set to 01 to activate the fast-lock mode, or
to 10 to activate a phase resync. In most applications, neither a
fast lock nor a phase resync is required. In this case, DB[20:19]
should be set to 00.
RESERVED BITS
All reserved bits should be set to 0 for normal operation.
INITIALIZATION SEQUENCE
After powering up the part, the correct register programming
sequence is as follows:
1. CLK DIV register (R4)
2. Function register (R3)
3. MOD/R register (R2)
4. Phase register (R1)
5. FRAC/INT register (R0)
DB31
DB30 DB29 DB28 DB27 DB26 DB25 DB24
DB23 DB22 DB21 DB20 DB19 DB18 DB17 DB16 DB15 DB14 DB13 DB12 DB11 DB10 DB9 DB8 DB7 DB6 DB5 DB4 DB3 DB2 DB1 DB0
0 0 0 0 0 0 0 0 0 0 0
M2 M1 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 R4 R3 R2 R1 C3(1) C2(0)
C1(0)
CONTROL
BITS
RESERVEDRESERVED
CLK
DIV
MODE
12-BIT CLOCK
DIVIDER
VALUE
M2 M1
CLK DIV MODE
0 0 CLK DIV OFF
0 1 FAST-LOCK MODE
1 0 R
ESYNC TIMER ENABLED
1 1
RESERVED
D12 D11
.......... D2 D1 CLOCK DIVIDER VALUE
0 0 .......... 0 0 0
0 0 .......... 0 1
1
0 0 .......... 1
0 2
0
0 .......... 1
1 3
. . .......... .
. .
. . ..........
. . .
. . .......... . . .
1 1 .......... 0 0 4092
1 1
.......... 0
1 4093
1 1 .......... 1 0 4094
1 1 ..........
1 1 4095
05863-015
Figure 21. CLK DIV Register (R4) Map
Data Sheet ADF4156
Rev. E | Page 17 of 24
RF SYNTHESIZER: A WORKED EXAMPLE
The following equation governs how the synthesizer should be
programmed:
RF
OUT
= [INT + (FRAC/MOD)] × [F
PFD
] (3)
where:
RF
OUT
is the RF frequency output.
INT is the integer division factor.
FRAC is the fractionality.
MOD is the modulus.
The PFD frequency can be calculated as follows:
F
PFD
= REF
IN
× [(1 + D)/(R × (1 + T))] (4)
where:
REF
IN
is the reference frequency input.
D is the RF REF
IN
doubler bit.
T is the reference divide-by-2 bit, which is set to 0 or 1.
R is the RF reference division factor.
For example, in a GSM 1800 system, 1.8 GHz RF frequency
output (RF
OUT
) is required, 13 MHz reference frequency input
(REF
IN
) is available, and 200 kHz channel resolution (f
RES
) is
required on the RF output.
MOD = REF
IN
/f
RES
MOD = 13 MHz/200 kHz = 65
Therefore, from Equation 4,
F
PFD
= [13 MHz × (1 + 0)/1] = 13 MHz (5)
1.8 GHz = 13 MHz × (INT + FRAC/65) (6)
where INT = 138 and FRAC = 30.
MODULUS
The choice of modulus (MOD) depends on the reference signal
(REF
IN
) available and the channel resolution (f
RES
) required at
the RF output. For example, a GSM system with 13 MHz REF
IN
sets
the modulus to 65, resulting in the required RF output resolution
(f
RES
) of 200 kHz (13 MHz/65). With dither off, the fractional spur
interval depends on the modulus values chosen. See Table 7 for
more information.
REFERENCE DOUBLER AND REFERENCE DIVIDER
The on-chip reference doubler allows the input reference signal
to be doubled. This is useful for increasing the PFD comparison
frequency, which in turn improves the noise performance of the
system. Doubling the PFD frequency usually improves noise
performance by 3 dB. It is important to note that the PFD cannot
operate with frequencies greater than 32 MHz due to a limitation
in the speed of the Σ-Δ circuit of the N-divider.
The reference divide-by-2 divides the reference signal by 2,
resulting in a 50% duty cycle PFD frequency. This is necessary
for the correct operation of the cycle slip reduction (CSR)
function. See the Fast Lock Times section for more information.
12-BIT PROGRAMMABLE MODULUS
Unlike most other fractional-N PLLs, the ADF4156 allows the user
to program the modulus over a 12-bit range. Therefore, several
configurations of the ADF4156 are possible for an application by
varying the modulus value, the reference doubler, and the 5-bit
R-counter.
For example, consider an application that requires 1.75 GHz RF
and 200 kHz channel step resolution. The system has a 13 MHz
reference signal.
One possible setup is feeding the 13 MHz directly into the PFD
and programming the modulus to divide by 65. This results in
the required 200 kHz resolution.
Another possible setup is using the reference doubler to create
26 MHz from the 13 MHz input signal. The 26 MHz signal is then
fed into the PFD, which programs the modulus to divide by 130.
This setup also results in 200 kHz resolution, but offers superior
phase noise performance compared with the previous setup.
The programmable modulus is also useful for multistandard
applications. If a dual-mode phone requires PDC and GSM
1800 standards, the programmable modulus is a great benefit.
The PDC requires 25 kHz channel step resolution, whereas
GSM 1800 requires 200 kHz channel step resolution.
A 13 MHz reference signal can be fed directly into the PFD, and
the modulus can be programmed to 520 when in PDC mode
(13 MHz/520 = 25 kHz). However, the modulus must be
reprogrammed to 65 for GSM 1800 operation (13 MHz/65
= 200 kHz).
It is important that the PFD frequency remains constant (13 MHz).
This allows the user to design one loop filter that can be used in
both setups without running into stability issues. It is the ratio
of the RF frequency to the PFD frequency that affects the loop
design. By keeping this relationship constant, the same loop
filter can be used in both applications.
FAST LOCK TIMES WITH THE ADF4156
As mentioned in the Noise and Spur Mode section, the ADF4156
can be optimized for noise performance. However, in fast-locking
applications, the loop bandwidth needs to be wide; therefore,
the filter does not provide much attenuation of the spurs.
There are two methods of achieving a fast lock time for the
ADF4156: using cycle slip reduction or using dynamic bandwidth
switching mode. In both cases, the idea is to keep the loop band-
width narrow to attenuate spurs while obtaining a fast lock time.
Cycle slip reduction mode is the preferred technique because it
does not require modifications to the loop filter or optimization
of the timeout counter values and is therefore easier to implement.

ADF4156BCPZ-RL

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Phase Locked Loops - PLL 6.2 GHz Fractional-N Freq Synthesizer
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union