SDR-480-24

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
Note.6
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.7
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
Note.5
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
DC OK REALY CONTACT RATINGS (max.)
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1500ms, 150ms/230VAC 3000ms, 150ms/115VAC at full load
14ms/230VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
94%
0.94/230VAC 0.99/115VAC at full load
5A/115VAC 2.5A/230VAC
56 ~ 65V
40A/115VAC 80A/230VAC
<0.8mA / 240VAC
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN60950-1 approved ; (meet EN60204-1)
, EAC TP TC 004
Compliance to EN55011, EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
-25 ~ +70 (Refer to "Derating Curve")
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
112.9K hrs min. MIL-HDBK-217F (25 )
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020, SEMI F47, GL approved
85.5*125.2*128.5mm (W*H*D)
1.6Kg; 8pcs/13.8Kg/0.9CUFT
POWER FACTOR (Typ.)
SDR-480-48
48V
10A
0 ~ 10A
480W
15A
120mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
SDR-480-24
24V
20A
0 ~ 20A
480W
30A
720W (3sec.)
100mVp-p
24 ~ 28V
±1.2%
±0.5%
±1.0%
Features :
SDR-480 series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
480W Single Output Industrial DIN RAIL with PFC Function
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.94
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
File Name:SDR-480-SPEC 2018-01-12
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
EMC IMMUNITY
EMC EMISSION
GL
PQ
S
E
M
I
F
4
7
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
Mechanical Specification
Case No.984A Unit:mm
+
Block Diagram
DC OK Relay Contact
DETECTION
PWM & PFC
CIRCUIT
O.L.P.U.V.P.
EMI FILTER
RECTIFIERS
POWER
SWITCHING
FILTER
&
RECTIFIERS
+V
DC OK
-V
I/P
FG
CONTROL
O.V.P.
&
O.C.P.
PFC
CIRCUIT
PFC
CONTROL
Contact Close PSU turns on / DC OK.
PSU turns off / DC Fail.
30V/1A resistive load.
Contact Open
Contact Ratings (max.)
SDR-480 series
480W Single Output Industrial DIN RAIL with PFC Function
1
2
3
4
5
6
7
8
1
2
3
125.2
TB2
TB1
128.5
85.5
+V ADJ
DC OK
DC OK
Terminal Pin No. Assignment (TB1)
Terminal Pin No. Assignment (TB2)
Pin No.
Pin No.
1
1,2
2
3,4
5,6
7,8
3
Assignment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
Relay Contact
NC
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
35
File Name:SDR-480-SPEC 2018-01-12
AMBIENT TEMPERATURE ( )
LOAD (%)
-25 0
Continuous
For 3 sec. (typ.)
230VAC
100VAC
10 20 30 40 50 55 60 70
60
80
100
120
150
(VERTICAL)
Output derating VS input voltageDerating Curve
INPUT VOLTAGE (V) 60Hz
LOAD (%)
40
110
50
60
70
80
155135 230 264
90
100
10090
Peak Loading
720W 720W
( 1 ) ( 2 )
480W 240W
50 sec. 15 sec.3 sec. 3 sec.
SDR-480 series
480W Single Output Industrial DIN RAIL with PFC Function
File Name:SDR-480-SPEC 2018-01-12

SDR-480-24

Mfr. #:
Manufacturer:
MEAN WELL
Description:
DIN Rail Power Supplies 480W 24V 20A W/PFC Function
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet