https://www.phoenixcontact.com/us/products/2838160
10/20/2014Page2/5
Lightning arrester type 1-FLT 100-260-2838160
Technical data
General
IEC power supply system TT
TN-S
Housing material PBT
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances EN 60664-1
EN 61643-11
Mounting type DIN rail: 35 mm
Type Rail-mountable module, one-piece
Number of positions 1
Surge protection fault message None
Direction of action N-PE
Protective circuit
IEC test classification I
T1
EN type T1
Nominal voltage U
N
230 V AC (400 V AC)
Maximum continuous operating voltage U
C
(N-PE)
260 V AC
U
T
(TOV-proof)
1200 V AC (200 ms)
Nominal frequency f
N
50 Hz
60 Hz
Residual current I
PE
≤ 0.1 mA
Standby power consumption P
C
≤ 26 mVA
Max. discharge current I
max
(8/20) µs
100 kA
Nominal discharge current I
n
(8/20) µs
100 kA
Nominal discharge current I
n
(8/20) µs (N-PE)
100 kA
Impulse discharge current (10/350)µs charge 50 As
Impulse discharge current (10/350)˽µs, specific energy 3 MJ/Ω
Impulse discharge current (10/350)˽µs, peak value l
imp
100 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 4 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE) ≤ 4 kV
Voltage protection level U
p
≤ 4 kV
Voltage protection level U
p
(N-PE)
≤ 4 kV
Response time ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Follow current quenching capacity If 100 A