Type 1 / Class I / B arrester (lightning current arrester) with encapsulated N-PE total spark gap, 1-channel.
Housing width: 35 mm (2 Div.)
Product Features
High discharge capacity
Single-channel
Key commercial data
Packing unit 1 pc
GTIN
Weight per Piece (excluding packing) 296.03 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 90 mm
Width 35.8 mm
Depth 65.7 mm
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) ≤ 95 %
https://www.phoenixcontact.com/us/products/2838160
10/20/2014Page2/5
Lightning arrester type 1-FLT 100-260-2838160
Technical data
General
IEC power supply system TT
TN-S
Housing material PBT
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances EN 60664-1
EN 61643-11
Mounting type DIN rail: 35 mm
Type Rail-mountable module, one-piece
Number of positions 1
Surge protection fault message None
Direction of action N-PE
Protective circuit
IEC test classification I
T1
EN type T1
Nominal voltage U
N
230 V AC (400 V AC)
Maximum continuous operating voltage U
C
(N-PE)
260 V AC
U
T
(TOV-proof)
1200 V AC (200 ms)
Nominal frequency f
N
50 Hz
60 Hz
Residual current I
PE
≤ 0.1 mA
Standby power consumption P
C
≤ 26 mVA
Max. discharge current I
max
(8/20) µs
100 kA
Nominal discharge current I
n
(8/20) µs
100 kA
Nominal discharge current I
n
(8/20) µs (N-PE)
100 kA
Impulse discharge current (10/350)µs charge 50 As
Impulse discharge current (10/350)˽µs, specific energy 3 MJ/Ω
Impulse discharge current (10/350)˽µs, peak value l
imp
100 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 4 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE) ≤ 4 kV
Voltage protection level U
p
≤ 4 kV
Voltage protection level U
p
(N-PE)
≤ 4 kV
Response time ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Follow current quenching capacity If 100 A
https://www.phoenixcontact.com/us/products/2838160
10/20/2014Page3/5
Lightning arrester type 1-FLT 100-260-2838160
Technical data
Protective circuit
Follow current quenching capacity If (N-PE) 100 A
Connection, protective circuit
Connection method Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M6
Tightening torque 8 Nm
Stripping length 19 mm
Conductor cross section stranded min. 16 mm²
Conductor cross section stranded max. 35 mm²
Conductor cross section solid min. 10 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG/kcmil min. 6
Conductor cross section AWG/kcmil max 1
Standards and Regulations
Standards/regulations IEC 61643-1 2005
EN 61643-11/A11 2007
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27140201
eCl@ss 5.0 27140201
eCl@ss 5.1 27140201
eCl@ss 6.0 27140201
eCl@ss 7.0 27140201
eCl@ss 8.0 27140201
ETIM
ETIM 2.0 EC000381
ETIM 3.0 EC000381
ETIM 4.0 EC000381
ETIM 5.0 EC000381

2838160

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Surge Suppressors FLT 100-260
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet