MODEL NUMBERS HPF240D20 HPF240D30 HPF480D20 HPF480D30
OUTPUT SPECIFICATIONS
➀
Operating Voltage (47-63 Hz) [Vrms] 12-280 12-280 48-660
⑥
48-660
⑥
Max. Load Current [Arms] 20 30 20 30
Min. Load Current, [mArms] 150 150 150 150
Transient Overvoltage [Vpk] 600 600 1200 1200
Max. Surge Current, (16.6ms) [Apk] 250 625 250 625
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.4 1.6 1.4
Maximum I
2
t for Fusing, (8.3 msec.) [I
2
sec] 260 1620 260 1620
Max. Off-State Leakage Current @ Rated Voltage [mArms] ➁ 0.1 0.1 0.1 0.1
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] ➂ 500 500 500 500
Max. Turn-On Time ④ 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Max. Turn-Off Time 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS ➀ DC CONTROL
(HPF240Dxx) (HPF480Dxx)
Control Voltage Range 4-32 Vdc 4.5-32 Vdc
Max. Turn-On Voltage 5.0 Vdc 5.0 Vdc
Min. Turn-Off Voltage 1.0 Vdc 1.0 Vdc
Nominal Input Impedance See Note ⑤ See Note ⑤
Typical Input Current @ 5Vdc 5 mAdc 5 mAdc
Typical Input Current @ 20Vdc 20 mAdc 20 mAdc
GENERAL NOTES
➀ All parameters at 25ºC unless otherwise specified.
➁ Off-State leakage for snubbered version (S suffix) is 10 mArms
➂ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➃ Turn-on time for random turn-on version is 0.02 msec.
⑤ Input circuitry incorporates active current limiter.
⑥ Operating voltage range for snubbered version (S-suffix) is 48-530 Vrms.
• DIN Rail Mount
• Integral Heat sink
• LED Status Indicator
• SCR Output
• Zero Voltage and Random
Turn-On Switching
• Low Leakage
FastFax Document No.155
SERIES HPF.032698, PAGE 1 OF 2
The Series HPF Solid State Relays utilize
Crydom’s proprietary thermal man-
agement technology providing a com-
pact and efficient design. Built-in DIN
Rail attachment, easy-to-use cage type
terminals and integral heat sinking
complete the package. This compact
new design offers up to 30Arms in
ambient temperatures of 25˚C.
Manufactured in Crydom’s ISO 9002
Certified facility for optimum product
performance and reliability.
Series HPF
20, 30Amp • 120/240/480 Vac • AC Output
©1998 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280
9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: sales@crydom.com
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191
UK: (44)1202 812300 • fax (44)1202 812340
85, Condor Close, Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU
GERMANY: (49)871 935405 • fax (49)871 935407, Aussere Parkstr.5, D-84032 Altdorf, Germany