B88069X2010S102

Surge arrester
2-electrode arrester
Series/Type: L71-A470X
Ordering code: B88069X2010****
Date: 2017-06-20
Version: 07
EPCOS AG 2017. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then
change the color to "white". This ensures that the table disappears (invisible) for the customer PDF.
Don't change formatting when entering or pasting text in the table and don't add any cell or line in and to it!
Identification/Classification 1
(header 1 + top left bar):
Surge arrester
Identification/Classification 2
(header 2 + bottom left header bar):
2-electrode arrester
Ordering code: (top right header bar)
B88069X2010****
Series/Type: (bottom right header bar)
L71-A470X
Preliminary data (optional):
Department:
PPD AB PD / PPD AB PM
Date:
2017-06-20
Version: 07
Surge arrester B88069X2010****
2-electrode arrester L71-A470X
PPD AB PD / PPD AB PM Version: 07 / 2017-06-20
Please read Cautions and warnings and Page 2 of 5
Important notes at the end of this document.
Features Applications
Standard size
High follow current capability
Very fast response time
Stable performance over life
Very low capacitance
High insulation resistance
RoHS-compatible
Application with high follow current
Power supply
Electrical specifications
DC spark-over voltage
1) 2)
Tolerance
Min.
Max.
470
-15 … +25
400
588
V
%
V
V
Impulse spark-over voltage
at 100 V/µs - for 99% of measured values
- typical values of distribution
at 1 kV/µs - for 99% of measured values
- typical values of distribution
< 700
< 600
< 800
< 700
V
V
V
V
Service life
10 operations 50 Hz, 1 s
5 A
1 operations 50 Hz, 0.18 s (9 cycles) 65 A
10 operations 8/20 µs 5 kA
1 operation 8/20 µs 10 kA
Max. follow current during one voltage half cycle at 50 Hz 200 A
Insulation resistance at 100 V
DC
> 10
G
Capacitance at 1 MHz < 1.5
pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 22
< 0.5
~ 160
V
A
V
Weight ~ 2 g
Operation and storage temperature
40 ... +125
°C
Climatic category (IEC 60068-1) 40/125/21
Marking, green positive
470 YY O
470 - Nominal voltage
YY - Year of production
O - Non radioactive
Certifications
UL 497B (E163070)
1)
At delivery AQL 0.65 level II, DIN ISO 2859
2)
In ionized mode
Terms in accordance with ITU-T Rec. K.12 and IEC 61643-311.
Surge arrester B88069X2010****
2-electrode arrester L71-A470X
PPD AB PD / PPD AB PM Version: 07 / 2017-06-20
Please read Cautions and warnings and Page 3 of 5
Important notes at the end of this document.
Dimensional drawing in mm
Ordering codes and packing advices
B88069X2010S102 = 100 pcs. on 5 taped stripes B88069X2010T502 = 500 pcs. on tape & reel