Specifications are subject to change without notice (06.06.05) 1
Proximity Sensors Inductive
Extended Range, Nickel Plated Brass Housing
Types IA, DC, M12, M18 and M30, 2-wire
• Sensing distance: 4 to 22 mm
• Flush and non-flush types
• Power supply: 10 to 40 VDC
• Output: Transistor
• Make or break switching
• Protection: Reverse polarity, short-circuit and transients
• 2 m cable or plug M12
•
Diameter: M12, M18, M30
Product Description
accordance with Euronorm
EN 60 947-5-2.
Proximity switch M12, M18
and M30 in nickel-plated
brass housings. Made in
Type Selection
Housing Body Connec- Rated Ordering no. Ordering no.
diameter style tion operating 2 wire DC 2 wire DC
dist. (S
n
) Normally open Normally closed
M12 Short Cable 4 mm
1)
IA 12 DSF 04 DO IA 12 DSF 04 DC
M12 Short Plug 4 mm
1)
IA 12 ASF 04 DO M1 IA 12 ASF 04 DC M1
M12 Short Cable 8 mm
2
)
IA 12 DSN 08 DO IA 12 DSN 08 DC
M12 Short Plug 8 mm
2)
IA 12 ASN 08 DO M1 IA 12 ASN 08 DC M1
M18 Short Cable 8 mm
1)
IA 18 DSF 08 DO IA 18 DSF 08 DC
M18 Short Plug 8 mm
1)
IA 18 ASF 08 DO M1 IA 18 ASF 08 DC M1
M18 Short Cable 14 mm
2)
IA 18 DSN 14 DO IA 18 DSN 14 DC
M18 Short Plug 14 mm
2)
IA 18 ASN 14 DO M1 IA 18 ASN 14 DC M1
M30 Short Cable 15 mm
1)
IA 30 DSF 15 DO IA 30 DSF 15 DC
M30 Short Plug 15 mm
1)
IA 30 ASF 15 DO M1 IA 30 ASF 15 DC M1
M30 Shor
t
Cable 22 mm
2)
IA 30 DSN 22 DO IA 30 DSN 22 DC
M30
Short
Plug
22 mm
2)
IA 30 ASN 22 DO M1
IA 30 ASN 22 DC M1
1)
For flush mounting in metal
2)
For non-flush mounting in metal
Ordering Key
Cap. proximity switch
Housing style
Housing size
Housing material
Housing length
Detection principle
Sensing distance
Output type
Output configuration
Connection
IA12ASF04DOM1
Specifications
Rated operational volt. (U
e
) 12 to 36 VDC
(U
B
)
10 to 40 VDC (ripple included)
Ripple ≤ 10%
Rated operational current (I
e
)
Continuous ≤ 5-100 mA
No-load supply current (I) ≤ 0.8 mA
Voltage drop (U
d
) ≤ 3 VDC at max. load
Protection Reverse polarity
,
short-circuit, transients
Transient voltage ≤ 1 kV/0.5 J
EMC Appr
oved according to
EN 50 080, EN 50 081
Power ON delay < 50 ms
Frequency of operating IA12xSF 1000 Hz
cycles (f) IA12xSN 800 Hz
IA18xSF 500 Hz
IA18xSN 400 Hz
IA30xSF 400 Hz
IA30xSN 200 Hz