TDUBH3002A

© 2016 Littelfuse Protection Relays & Controls
Time Delay Relays
Dedicated - Delay-on-Break
www.littelfuse.com/
Rev: 1-A-062116
www.littelfuse.com/tdub
TDUB SERIES
L1 N/L2
Description
The TDUB Series combines digital timing circuitry with universal
voltage operation. Voltages of 24 to 240VAC and 12 to 24VDC
are available in three ranges. The TDUB Series offers DIP switch
selectable time delays ranging from 0.1 seconds to 102.3
minutes in three ranges. Its 1A rated output, ability to operate
on multiple voltages, and wide range of switch selectable time
delays make the TDUB Series an excellent choice for process
control systems and OEM equipment.
Operation (Delay-on-Break)
Input voltage must be applied before and during timing.
Upon closure of the initiate switch, the output energizes. The
time delay begins when the initiate switch is opened (trailing
edge triggered). The output remains energized during timing.
At the end of the time delay, the output de-energizes. The output
will energize if the initiate switch is closed when input voltage is
applied.
Reset: Reclosing the initiate switch during timing resets the time
delay. Loss of input voltage resets the time delay and output.
Features & Benefits
FEATURES BENEFITS
Dip Switch Timing
Adjustment
Provides setting accuracy of +/-2%
User selectable
time delay
Timing settings are switch selectable 0.1s - 102.3m
in three ranges for added flexibility
1A steady, 10A inrush
solid-state output
Provides 100 million operations in typical conditions.
Totally solid state
and encapsulated
No moving parts to arc and wear out over time and
encapsulated to protect against shock, vibration,
and humidity.
Accessories
P1015-13 (AWG 10/12), P1015-64 (AWG 14/16),
P1015-14 (AWG 18/22) Female Quick Connect
These 0.25 in. (6.35 mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with
all modules with 0.25 in. (6.35 mm) male quick
connect terminals.
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.
Wiring Diagram
V = Voltage
UTL = Optional Untimed Load
S1 = Initiate Switch
L = Timed Load
Delay-on-Break Timer
Ordering Information
MODEL INPUT VOLTAGE RANGE TIME RANGE
TDUB3000A 24 to 120VAC 1-1023s
TDUB3002A 12 to 24VDC 1-1023s
TDUBH3002A 12 to 24VDC 0.1-102.3m
TDUBH3001A 100 to 240VAC 0.1-102.3m
TDUBL3002A 12 to 24VDC 0.1-102.3s
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
Time Delay Relays
Dedicated - Delay-on-Break
www.littelfuse.com/
Rev: 1-A-062116
www.littelfuse.com/tdub
Specifications
Time Delay
Range* 0.1 - 102.3s in 0.1s increments
1 - 1023s in 1s increments
0.1 - 102.3m in 0.1m increments
Repeat Accuracy ±0.5% or 20ms, whichever is greater
Setting Accuracy ≤ ±2% or 20ms, whichever is greater
Reset Time 150ms
Initiate Time ≤ 20ms
Time Delay vs. Temperature
& Voltage ≤ ±5%
Input
Voltage/Tolerance 24 to 240VAC, 12 to 24VDC /±20%
AC Line Frequency/DC Ripple 50/60 Hz / ≤ 10%
Power Consumption AC ≤ 2VA; DC ≤ 1W
Output
Type Solid state
Form NO, closed before and during timing
Rating 1A steady state, 10A inrush at 60°C
Voltage Drop AC 2.5V @ 1A; DC 1V @ 1A
Off State Leakage Current AC 5mA @ 230VAC; DC 1mA
Protection
Circuitry Encapsulated
Dielectric Breakdown ≥ 2000V RMS terminals to mounting surface
Insulation Resistance ≥ 100 M
Polarity DC units are reverse polarity protected
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 50.8 mm (2”); W 50.8 mm (2”);
D 30.7 mm (1.21”)
Termination 0.25 in. (6.35 mm) male quick connect
terminals
Environmental
Operating/Storage
Temperature -40° to 60°C /-40° to 8C
Humidity 95% relative, non-condensing
Weight 2.4 oz (68 g)
*For CE approved applications, power must be removed from the unit when a switch position
is changed.
TDUB SERIES
Add the value of switches in the ON position
for the total time delay.
Adjustment Switch Operation
Adjustment Switch Operation
Function Diagram
DELAY-ON-BREAK (OFF-DELAY)
V = Voltage
S1 = Initiate Switch
NO = Normally
Open Contact
NC = Normally
Closed Contact
TD = Time Delay
t = Incomplete
Time Delay
R = Reset
= Undefined
Time

TDUBH3002A

Mfr. #:
Manufacturer:
Littelfuse
Description:
Time Delay & Timing Relays DIGI-SETTIMER-DELAYO NBREAK
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet