SPECIFICATION
DR-75-12 DR-75-24 DR-75-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
12V 24V 48V
6.3A 3.2A 1.6A
0 ~ 6.3A 0 ~ 3.2A 0 ~ 1.6A
76W 76.8W 76.8W
100mVp-p 150mVp-p 240mVp-p
±2.0% ±1.0% ±1.0%
12 ~ 14V 24 ~ 28V 48 ~ 53V
±0.5% ±0.5% ±0.5%
±1.0% ±1.0% ±1.0%
85 ~ 264VAC 120 ~ 370VDC
47 ~ 63Hz
76% 80% 81%
1.6A/115V 0.96A/230V
COLD START 20A/115VAC 40A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V 29 ~ 34V 58 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
85 5 (TSW1) detect on heat sink of power transistor℃± ℃
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN60950-1 approved
, EAC TP TC 004
Compliance to EN55011,EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
-10 ~ +60 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH℃
±℃ ℃)0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
123.1K hrs min. MIL-HDBK-217F (25 )℃
55.5*125.2*100mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
File Name:DR-75-SPEC 2018-01-12
1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load
60ms/230VAC 12ms/115VAC at full load
75W Single Output Industrial DIN Rail Power Supply
DR-75 series
Universal AC input / Full range
Protections:Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 50KHz
3 years warranty
■
Features :
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note 4)
EMC IMMUNITY
EMC EMISSION
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os