EVAL-ADP1740/ADP1741
Rev. 0 | Page 5 of 12
LINE REGULATION
For line regulation measurements, the regulator output is
monitored while its input is varied. For good line regula-
tion, the output must change as little as possible with varying
input levels.
To ensure that the device is not in dropout mode during this
measurement, V
IN
must be varied between V
OUTNOM
+ 0.4 V
(or + 1.6 V, whichever is greater) and V
INMAX
. For example, for
an ADP1740 with fixed 1.5 V output, V
IN
needs to be varied
between 1.9 V and 3.6 V. This measurement can be repeated
under different load conditions. Figure 4 shows the typical line
regulation performance of an ADP1740 with fixed 1.5 V output.
1.520
1.515
1.510
1.505
1.500
1.495
1.490
1.485
1.480
1.8 2.0 2.4 2.8 3.6
07154-004
OUTPUT VOLTAGE (V)
V
IN
(V)
2.2 2.6 3.0 3.2 3.4
LOAD = 10mA
LOAD = 100mA
LOAD = 400mA
LOAD = 800mA
LOAD = 1.2A
LOAD = 2A
Figure 4. Output Voltage vs. Input Voltage
LOAD REGULATION
For load regulation measurements, the output of the regulator
is monitored while the load is varied. For good load regulation,
the output must change as little as possible with varying loads.
The input voltage must be held constant during this measure-
ment. The load current can be varied from 500 A to 2 A. Figure 5
shows the typical load regulation performance of an ADP1740
with fixed 1.5 V output for an input voltage of 1.9 V.
1.520
1.515
1.510
1.505
1.500
1.495
1.490
1.485
1.480
10
10k
OUTPUT VOLTAGE (V)
100 1k
LOAD CURRENT (mA)
07154-005
Figure 5. Output Voltage vs. Load Current
DROPOUT VOLTAGE
Dropout voltage can be measured using the configuration
shown in Figure 3. Dropout voltage is defined as the input-to-
output voltage differential when the input voltage is set to the
nominal output voltage. This applies only for output voltages
above 1.6 V. Dropout voltage increases with larger loads.
For more accurate measurements, use a second voltage meter
to monitor the input voltage across the input capacitor. The
input supply voltage may need to be adjusted to account for IR
drops, especially if large load currents are used. Figure 6 shows
a typical curve of dropout voltage measurements with different
load currents.
0.25
0.20
0.15
0.10
0.05
0
101
10k
DROPOUT VOLTAGE (mV)
100 1k
LOAD CURRENT (mA)
07154-006
1.6V
2.5V
Figure 6. Dropout Voltage vs. Load Current