E5C2
E5C2
2
Part number E5C2-❑❑❑K E5C2-❑❑❑J E5C2-❑❑❑P-DIN E5C2-❑❑❑G
Sensor input types Thermocouple type K Thermocouple type J Platinum RTD Thermistor
Supply voltage 100/120 VAC, 50/60 Hz or 220/240 VAC, 50/60 Hz
Operating voltage 90 to 110% of rated supply voltage
Power consumption Approx. 2 VA
Control Number One output, built in
output Type Relay SPDT, 3 A, 250 VAC (resistive load), switching capacity of 330 VA
Voltage 5 VDC, 10 mA with short-circuit protection
Hysteresis 0.5% max. of full scale (fixed)
Service life 100,000 electrical operations minimum for relay output
10 million mechanical operations minimum for relay output
Alarm output Not available
Setting accuracy ±2% maximum of full scale
Control Type ON/OFF (E5C2-❑20❑) or PD (E5C2-❑40❑)
modes Proportional band 3% of full scale (fixed)
Reset 3% minimum of full scale (variable); front panel potentiometer adjustment
Control period Approx. 20 seconds, where ratio of ON to OFF is 1:1
Memory protection Not available
Indicators Operation Indicator (red LED)
Materials Plastic case
Mounting Fits 1/16 DIN panel cutouts; includes panel mounting adapter Y92F-30
Connections Terminals for standard 8-pin round connectors
Weight Approx. 200 g (7 oz.)
Enclosure Front panel IEC IP40, NEMA 4 with optional cover Y92A-48N
ratings Housing IEC IP20
Terminals IEC IP00
Approvals UL Recognized, File No. E68481, approved control output rating 1.5 A, 250 VAC
CSA Certified, File No. LR59623, approved control output rating 1.5 A, 250 VAC
Other SEV, File No. D4.11/634
Ambient Use -10° to 55°C (14° to 131°F)
temperature Storage -25° to 65°C (-13° to 149°F)
Humidity 35 to 85% RH
Insulation resistance 20 MΩ minimum at 500 VDC
Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute
Vibration Mechanical 10 to 55 Hz 0.75 mm (0.03 in) in X, Y, and Z directions for 2 hours each
Malfunction 2 to 55 Hz, 2 G, in X, Y, and Z directions for 10 minutes each
Shock Mechanical 300 m/s
2
in 6 directions, 3 times each
Malfunction 200 m/s
2
in 6 directions, 3 times each
■ ACCESSORIES
Description Part number
Sockets Bottom surface or track mounting, top screw terminals P2CF-08
Back mounting, for use with Y92F-30 mounting adapter supplied, bottom screw temrinals P3G-08
Back mounting plug type, for use with Y92F-30 mounting adapter supplied US08
Protective cover Hard plastic cover protects against accidental resetting. Y92A-48B
Mounting track DIN rail, 50 cm (1.64 ft) length PFP-50N
DIN rail, 1 m (3.28 ft) length PFP-100N
End plate PFP-M
Spacer PFP-S
Specifications
■ REPLACEMENT PART
Description Part number
Panel mounting bracket; one supplied with each controller Y92F-30