4435.0018

1
Thermal (T- and TA-Line)
TA35 Rocker 3Pole
https://www.schurter.com /PG17_20
Circuit Breakers
Circuit Breaker for Equipment thermal, Rocker actuation, 3 poles
See below:
Approvals and Compliances
Description
- Thermal circuit breaker
- 3-pole
- Snap-in version
- Positively trip-free release
- Different rocker colours
- High configurability
- Wide current range
Applications
- Power tools
- Industrial appliances
- Equipment for construction
- Cleaning equipment
- Commercial and household kitchen appliances
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC 415 Y / 240 V; 50/60 Hz
Rated current range AC 0.05 - 12 A
Conditional short circuit ca-
pacity
0.05...12 A: 2 kA @ 415 VAC
Degree of Protection from front side IP 40 acc. to IEC 60529
Dielectric Strength 50 Hz: > 2.5 kV
Impulse 1.2/50 μs: > 4 kV
Insulation Resistance 500 VDC > 100 MΩ
Lifetime mechanical: 50'000 switching cycles
AC: 1 x Ir, cos φ 0.6:
50'000 switching cycles
DC: 1 x Ir, L/R = 2 - 3 ms:
50'000 switching cycles
Overload IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
Ambient temperature -30 °C to 60 °C
Vibration Resistance ± 0.75 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Tc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Tc
Shock Resistance 30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Tripping Type Thermal
Actuation Type Rocker
Weight 43.0 - 45.0 g
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: TA35
Approval Logo Certificates Certification Body Description
VDE Approvals VDE VDE Certificate Number: 40019754
UL Approvals UL UL File Number: E71572
CQC Approvals CQC CCC Certificate Number: 2013010307598660
2
Thermal (T- and TA-Line)
TA35 Rocker 3Pole
https://www.schurter.com /PG17_20
Circuit Breakers
Product standards
Product standards that are referenced
Organization Design Standard Description
Designed according to IEC 60934 Circuit-breakers for equipment (CBE)
Designed according to UL 1077 Standard for Supplementary Protectors for Use in Electrical Equipment
Designed according to CSA C22.2 No. 235 Supplementary Protectors
Designed according to GB 17701 Circuit-breaker for equipment
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG EU Directive RoHS 2011/65/EU
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Dimension [mm]
21.3
36
33.8
2.3
44.1 1.7
10.5 7.2
34
11 11 6.1
40.5
34.5
37.4
33.5
10.6
31.9
6.3 x 0.8 mm
LINE
L
37.5
34
+0.2
0
+0.2
0
+
0
.
3
Panel 1.0 − 4.0 mm
Diagrams
3-pole, 3 bimetal, illuminated
P1
4
P2
5
P3
6
1)
2)
1) Line, 2) Load
Codepos AAA = CD1
3-pole, 3 bimetal, non illuminated
P1
4
P2
5
P3
6
1)
2)
1) Line, 2) Load
Codepos AAA = CKD, CLD
3
Thermal (T- and TA-Line)
TA35 Rocker 3Pole
https://www.schurter.com /PG17_20
Circuit Breakers
The keys / codepos are listed in the key table of the basic function for selection.
Approvals
Approval Rated current Rated voltage AC Rated voltage DC
UL 1077 0.05...12 A 415 Y/ 240 V -
CSA C22.2
235
0.05...12 A 415 Y/ 240 V -
IEC 60934 0.05...12 A 415 Y/ 240 V -
GB 17701 0.05...12 A 415 Y/ 240 V -
Typical internal resistance
Rated Current [A] Internal Resistance []
0.05 200.000
0.1 70.000
0.5 2.750
1.0 0.720
1.5 0.340
2.0 0.187
2.5 0.115
2.8 0.089
3.0 0.059
4.0 0.059
5.0 0.044
6.0 0.028
7.0 0.0142
8.0 0.0142
10.0 0.0109
12.0 0.0086
13.0 0.0072
14.0 0.0072
15.0 0.0056
16.0 0.0056
18.0 0.0052
20.0 0.0052
TA35 Rocker 3-poles max. 12 A
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C] Correction factor
-30 0.76
-20 0.81
0 0.90
+23 1.00
+40 1.06
+50 1.10
+60 1.14
Example: Rated current = 5 A; Environmental temperature = 50 °C; --> Correction factor =
1.10; Resulting current = 5.2 A --> Fount to next higher rated current: 6 A