FN3359-150-28

DATASHEET
3-Phase Filters FN 3359
High-current EMC/RFI Filter
Off-the-shelf high power filter for rated
currents up to 2500 A
HV versions applicable for IT power networks
Busbars for convenient and universal electrical
connection
Protective plastic covers optionally available for
unsurpassed safety
Performance indicators
Technical specifications
Maximum continuous operating voltage
3x 520/300 VAC (FN 3359)
3x 760/440 VAC (FN 3359 HV)
Operating frequency
DC to 60 Hz
Rated currents
150 to 2500 A @ 50°C
High potential test voltage
P –> E 2750 VDC for 2 sec (FN 3359)
P –> P 2250 VDC for 2 sec (FN 3359)
P –> E 3200 VDC for 2 sec (FN 3359 HV)
P –> P 3270 VDC for 2 sec (FN 3359 HV)
Protection category
IP 00
Overload capability
4x rated current at switch on,
1.5x rated current for 1 minute, once per hour
Temperature range (operation and storage)
-25°C to +100°C (25/100/21)
Flammability corresponding to
UL 94 V-2 or better
Design corresponding to
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
MTBF @ 45°C/480 V (Mil-HB-217F)
130,000 hours
Approvals
UL up to 1000A: 600/400 VAC; ENEC up to 1600A: 690/
400 VAC
Features and benefits
High-power filter for Class A compliance. With
approval measurement also Class B compliance
possible for some applications
Extremely compact high-current filter solution with
minimum space requirement
FN 3359 HV versions are applicable for IT power
networks
Optionally available transparent protective covers
for all filters up to 1000 A, to protect the installer,
operator or inspector from undeliberate touching of
life conductors. They can easily be retrofitted even if
the filter is already installed and connected
FN 3359 also improves conducted immunity of
installations
Typical applications
High-power motor drives, inverters and converters
Industrial three-phase systems
Entire factories, plants and installations
Large UPS
Machinery
Mining equipment
Photovoltaic systems with galvanic isolation*
Wind turbines
* For EMI solutions for PV system without galvanic
isolation, please contact your local Schaffner partner.
Typical electrical schematic
2 EMC/EMI Products Schaffner Group Datasheets 2018
Filter selection table
Filter Rated current
@ 50°C (40°C)
Typical drive
power rating*
Leakage current**
@ 520/760 VAC/50 Hz
Power loss
@ 25°C/50 Hz
Input/Output
connections
Weight Protective
covers***
[A] [kW] [mA] [W]
[kg] Order code
FN 3359-150-28 150 (164) 75 5.1 24 –28 5.8 801917
FN 3359-180-28 180 (197) 90 5.1 34 –28 5.8 801917
FN 3359-250-28 250 (250) 132 5.1 49 –28 9.0 801918
FN 3359-320-99 320 (350) 160 5.1 19 –99 10.5 801919
FN 3359-400-99 400 (438) 220 5.1 29 –99 10.5 801919
FN 3359-600-99 600 (657) 315 5.1 44 –99 11.0 801920
FN 3359-800-99 800 (876) 400 5.3 39 –99 20.0 806276
FN 3359-1000-99 1000 (1095) 560 5.3 60 –99 20.0 806276
FN 3359-1600-99 1600 (1600) 900 5.1 131 –99 27.0 n.a.
FN 3359-2500-99 2500 (2500) 1320 5.1 300 –99 69.0 n.a.
FN 3359 HV-150-28 150 (164) 110 7.5 24 –28 6.0 801917
FN 3359 HV-180-28 180 (197) 132 7.5 34 –28 6.0 801917
FN 3359 HV-250-28 250 (250) 200 7.5 49 –28 9.5 801918
FN 3359 HV-320-99 320 (350) 250 7.5 19 –99 10.5 801919
FN 3359 HV-400-99 400 (438) 315 7.5 29 –99 10.5 801919
FN 3359 HV-600-99 600 (657) 500 7.5 44 –99 11.0 801920
FN 3359 HV-800-99 800 (876) 630 7.5 39 –99 21.0 806276
FN 3359 HV-1000-99 1000 (1095) 710 7.5 60 –99 21.0 806276
FN 3359 HV-1600-99 1600 (1600) 1320 7.5 131 –99 27.0 n.a.
FN 3359 HV-2500-99 2500 (2500) 2000 7.7 300 –99 69.0 n.a.
* Calculated at rated current, 480 VAC (FN 3359)/690 VAC (FN 3359 HV ) and cos phi=0.8. The exact value depends upon the efficiency of the drive, the motor and the entire
** application.
** Standardized calculated leakage current acc. IEC60939 under normal operating conditions (FN 3359 at 520 VAC and FN 3359 HV at 760 VAC).
*** Please contact your local Schaffner partner to order the optional protective covers with the order code in the table above (n.a.: not available)
Typical filter attenuation
Per CISPR 17; A=50 Ω/50 Ω sym; B=50 Ω/50 Ω asym; C=0.1 Ω/100 Ω sym; D=100 Ω/0.1 Ω sym
150 to 180 A types
250 to 600 A types
800 and 1000 A types
1600 and 2500 A types
3 EMC/EMI Products Schaffner Group Datasheets 2018
Mechanical data
150 to 250 A types 320 to 2500 A types
Busbar connections
320 to 1000 A types 1600 A types 2500 A types
Dimensions
150 A 180 A 250 A 320 A 400 A 600 A 800 A 1000 A 1600 A 2500 A
A 300 300 300 300 300 300 350 350 400 450
B 210 210 230 260 260 260 280 280 300 370
C 120 120 125 115 115 135 170 170 160 220
D 160 160 180 210 210 210 230 230 250 300
E 120 120 120 120 120 120 145 145 170 200
F 185 185 205 235 235 235 255 255 275 330
G Ø12 Ø12 Ø12 Ø12 Ø12 Ø12 Ø12 Ø12 Ø12 Ø14
H 2 2 2 2 2 2 3 3 3 3
I 33 33 33 43 43 43 53 53 93 110
J M10 M10 M10 M12 M12 M12 M12 M12 M12 M12
K 55 55 62.5 20 20 20 25 25 25 25
L 30 30 35 20 20 20 25 25 25 25
M 420 420 420 440 440 440 510 510 n.a. n.a.
N 171 171 191 221 221 221 241 241 n.a. n.a.
O 127 127 132 122 122 142 177 177 n.a. n.a.
R 37 37 37 68 68 68 85
S 26 35
T 26 35
U 50 50 55 60 60 60 60 60 60 100
V 25 25 25 40 40 60 80
W 6 6 8 8 8 10 15
X 15 15 15 20 20 17 20
Y 40 40 40 50 50 93 110
Z Ø10.5 Ø10.5 Ø10.5 Ø14 Ø14 Ø14 Ø14
All dimensions in mm; 1 inch = 25.4 mm
Tolerances according: ISO 2768-m/EN 22768-m
(n.a.: not applicable)
Please visit www.schaffner.com
to find more details on filter connectors.

FN3359-150-28

Mfr. #:
Manufacturer:
Schaffner
Description:
Power Line Filters 3 PHASE 150A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union