Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F...
www.e-t-a.de
1708
1
1
Description
Typical application
Technical data
Single and multipole magnetic circuit breakers with trip-free
mechanism and toggle actuation. A choice of fast magnetic only or
hydraulically delayed switching characteristics (S-type MO or HM
CBE to EN 60934) ensures suitability for a wide range of applications.
Industry standard dimensions and panel mounting. Options include
auxiliary changeover contacts. Low temperature sensitivity at rated
load.
Approved to CBE standard EN 60934 (IEC 60934).
Control equipment, communications systems, transportation, power
supplies.
8340-F...
1-pole 2-pole
For further details please see chapter: Technical Information
Voltage rating 3 AC 415 V; AC 240 V, 50/60 Hz; DC 80 V
(higher DC ratings to special order)
Current ratings 0.02...50 A DC
0.02...30 A AC
Auxiliary circuit 6 A, AC 240 V;
3 A, DC 28 V
1 A, DC 65 V;
0.5 A, DC 80 V
Typical life
3 AC 415 V, AC 240 V:
0.02...30 A 6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
DC 80 V: 0.02...25 A 6,000 operations at 1 x I
N
, inductive
0.02...30 A 10,000 operations at 1 x I
N
, resistive
40 + 50 A 6,000 operations at 1 x I
N
, resistive
Ambient temperature -40...+85 °C (-40...+185 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area test voltage AC 3,000 V
Line to Load test voltage AC 1,500 V
pole to pole
(2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 3,000 V
switching to trip circuit test voltage AC 1,500 V
(version -X)
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity 6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity I
N
0.02...20 A 25...30 A
(UL 1077) AC: 1-pole AC 250 V/3,500A AC 250 V/3,500A
2-pole AC 250 V/3,500A AC 250 V/5,000A
3-pole 3AC 250V/3,500A 3AC250V/5,000A
DC: 1-pole 0.02...50 A DC 80 V/3,500 A
2-pole 0.02...30 A DC 80 V/3500 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration
with toggle down: 10 g (57-2000Hz) ± 0.76 mm (10-57 Hz)
at 0.9 x IN
directions 1, 2, 3, 4, 5: 10 g (57-2000 Hz) at 1 x IN.
Shock 100 g (11 ms) at 1 x IN, directions 1,2,3,4,5
100 g (11 ms) at 0.8 x IN, direction 6.
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 65 g per pole
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal resistance values (Ω) per pole
F1 F2 K1, M1, T1 K2, M2, T2
0,02 1 493 953 2 669 2 457
0,05 276 152 452 376
0,1 58 37 100 94
0,25 8,2 6,0 15,5 14,7
0,5 2,3 1,47 3,9 3,2
0,75 0,98 0,63 1,65 1,56
1 0,58 0,35 0,95 0,90
2 0,145 0,096 0,26 0,20
2,5 0,096 0,061 0,15 0,15
3 0,065 0,048 0,10 0,10
5 0,025 < 0,02 0,042 0,040
6 < 0,02 < 0,02 0,029 0,028
8 < 0,02 < 0,02 < 0,02 < 0,02
10 < 0,02 < 0,02 < 0,02 < 0,02
12 < 0,02 < 0,02 < 0,02 < 0,02
15 < 0,02 < 0,02 < 0,02 < 0,02
16 < 0,02 < 0,02 < 0,02 < 0,02
20 < 0,02 < 0,02 < 0,02 < 0,02
25 < 0,02 < 0,02 < 0,02 < 0,02
30 < 0,02 < 0,02 < 0,02 < 0,02
40 < 0,01 - < 0,01 -
50 < 0,01 - < 0,01 -