https://www.phoenixcontact.com/pi/products/2800623
04/30/2017Page2/4
Type 2 surge protection plug-VAL-MS 600DC-PV-ST-2800623
Technical data
General
Connection configuration Y configuration
Installation location Inside
Accessibility Accessible
Installation location of the disconnect device Internal
Mounting type On base element
Color jet black RAL 9005
Housing material PA 6.6-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Design Male
Number of positions 1
Surge protection fault message optical
Additional descriptions
Note
The UL data applies for the series connection of two surge protective
devices of the same type.
Protective circuit DC voltage side (DC)
Maximum continuous operating voltage U
CPV
400 V DC
Open circuit voltage U
OCSTC
≤ 330 V DC
Short-circuit current rating I
SCPV
1000 A
Continuous operating current I
CPV
20 µA
Standby power consumption P
C
≤ 25 mVA
Nominal discharge current (8/20) µs 15 kA
Maximum discharge current I
max
(8/20) µs
40 kA
Voltage protection level U
p
≤ 1.4 kV
Residual voltage U
res
≤ 1.4 kV (at I
n
)
≤ 1.1 kV (at 5 kA)
≤ 1.3 kV (at 10 kA)
≤ 1.5 kV (at 20 kA)
≤ 1.8 kV (at 30 kA)
≤ 2 kV (at 40 kA)
Response time t
A
≤ 25 ns
Insulation resistance R
iso
> 5 GΩ (at 500 V DC)
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV (L+) - G 800 V DC
Nominal voltage 670 V DC
Mode of protection (L+) - G
Power distribution system 1
Measured limiting voltage MLV (L+) - G 1550 V