B72242L0271K102

Characteristics (T
A
= 25 °C)
Ordering code
Type
SIOV-
V
v
(1 mA)
V
V
v
(1 mA)
%
v
c,max
(i
c
)
V
i
c
A
C
typ
(1 kHz)
pF
Bent strap terminals
B72242L0251K100 LS42K250QP 390 ±10 650 300 2900
B72242L0271K100 LS42K275QP 430 ±10 710 300 2700
B72242L0321K100 LS42K320QP 510 ±10 840 300 2300
B72242L0381K100 LS42K385QP 620 ±10 1025 300 1900
B72242L0421K100 LS42K420QP 680 ±10 1120 300 1800
B72242L0441K100 LS42K440QP 715 ±10 1180 300 1700
B72242L0461K100 LS42K460QP 750 ±10 1240 300 1600
Straight strap terminals
B72242L0251K102 LS42K250QPK2 390 ±10 650 300 2900
B72242L0271K102 LS42K275QPK2 430 ±10 710 300 2700
B72242L0321K102 LS42K320QPK2 510 ±10 840 300 2300
B72242L0381K102 LS42K385QPK2 620 ±10 1025 300 1900
B72242L0421K102 LS42K420QPK2 680 ±10 1120 300 1800
B72242L0441K102 LS42K440QPK2 715 ±10 1180 300 1700
B72242L0461K102 LS42K460QPK2 750 ±10 1240 300 1600
Strap varistors B722*
HighE, SuperioR, LS42 series
Page 4 of 12Please read Cautions and warnings and
Important notes at the end of this document.
Dimensional drawings
Bent strap terminals
SIOV-LS42K ... QP
Weight: 25 ... 40 g
Ordering code
th
max
mm
L ±1.0
mm
Bent strap terminals
B72242L0251K100 9.2 2.1
B72242L0271K100 9.4 1.9
B72242L0321K100 9.9 1.5
B72242L0381K100 10.6 0.8
B72242L0421K100 10.9 0.5
B72242L0441K100 11.1 0.4
B72242L0461K100 11.4 0.2
Straight strap terminals
B72242L0251K102 9.2 5.3
B72242L0271K102 9.4 5.5
B72242L0321K102 9.9 5.9
B72242L0381K102 10.6 6.5
B72242L0421K102 10.9 6.8
B72242L0441K102 11.1 7.0
B72242L0461K102 11.4 7.2
Straight strap terminals
SIOV-LS42K ... QPK2
Weight: 25 ... 40 g
Strap varistors B722*
HighE, SuperioR, LS42 series
Page 5 of 12Please read Cautions and warnings and
Important notes at the end of this document.
Reliability data
Test Test methods/conditions Requirement
Varistor voltage The voltage between two terminals with
the specified measuring current applied
is called V
V
(1 mA
DC
@ 0.2 ... 2 s).
To meet the specified value
Clamping voltage The maximum voltage between two
terminals with the specified standard
impulse current (8/20 µs) applied.
To meet the specified value
Max. DC operating
voltage
The maximum allowable DC operating
voltage V
DC
at UCT +5/–0 °C is applied
for 1000 ±48 h.
The leakage current I
leak
(t) during test is
recorded.
Then the specimen shall be stored at
room temperature and normal humidity
for 1 to 2 h.
Thereafter, the change of V
V
shall be
measured.
I
leak
(t = 1000 h) I
leak
(t = 0 h)
|V/V (1 mA)| 10%
Surge current derating,
8/20 µs
10 surge currents (8/20 µs), unipolar,
interval 60 s, amplitude corresponding
to derating curve for 10 impulses at
20 µs
|V/V (1 mA)| 10%
(measured in direction of
surge current)
No visible damage
Fast temperature cycling IEC 60068-2-14, test Na, LCT/UCT,
dwell time 30 min, 5 cycles
|V/V (1 mA)| 10%
No visible damage
Damp heat, steady state IEC 60068-2-78
The specimen shall be subjected to
40 ±2 °C, 90 to 95% r. H. for 56 ±2 days
with 10% of the maximum continuous
DC operating voltage V
DC
.Then stored
at room temperature and normal
humidity for 1 to 2 h.
Thereafter, the change of V
V
shall be
measured.
|V/V (1 mA)| 10%
Note:
UCT = Upper category temperature
LCT = Lower category temperature
Strap varistors B722*
HighE, SuperioR, LS42 series
Page 6 of 12Please read Cautions and warnings and
Important notes at the end of this document.

B72242L0271K102

Mfr. #:
Manufacturer:
EPCOS / TDK
Description:
Varistors 42mm / 275v
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union