Thermal-Magnetic Circuit Breakers 3500/4000
www.e-t-a.com
06/07 2 - 51
2
Description
Typical applications
Ordering information Technical data
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a flange for panel mounting, and optional
auxiliary contacts and unprotected shunt tap terminal. Type 4000 offers
lower internal resistance values and is fitted as standard with auxiliary
contacts and an intermediate reset position in which all contacts are
isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Control systems, instrumentation, medical equipment, machine tools,
robotics, communications systems.
3500 4000
standard type low-resistance type
Type No.
3500 standard version
4000 low resistance version
Mounting (optional)
F11 flange with additional M3 insertion nuts
Terminal design
P10 blade terminals 6.3-0.8 (QC .250), tinned
K20 screw terminals M3.5x5.5 with clamp
(not with -Si or type 4000)
Shunt terminal (optional)
A3 same as main terminals
(up to I
N
= 7 A, max. load 5 A)
Auxiliary contacts (optional with type 3500)
Si auxiliary contacts, silver plated
terminals one each N/O and N/C
ZR-Si auxiliary contacts with intermediate
position (standard with type 4000)
Current ratings
0.05...16 A (type 3500)
0.05...10 A (type 4000)
3500 - .. - P10 - A3 - Si - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current rating range 3500: 0.05...16 A
4000: 0.05...10 A
Auxiliary circuit 1 A, AC 240 V / DC 65 V
Typical life 5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7 AC 840 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
3500 4000
0.05...0.8 A 0.05...0.2 A self-limiting
1...2 A 0.3...2 A 200 A
2.5...16 A 2.5...10 A 400 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...16 A AC 250 V 1,000 A
type 3500: 0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-3, test Ca
Mass approx. 40 g
Current Internal resistance (Ω) Current Internal resistance (Ω)
ratings (A) 3500 4000 ratings (A) 3500 4000
0.05 447 211 3 0.19 0.054
0.1 131 48 4 0.090 0.035
0.2 40 12.4 5 0.061 0.025
0.3 19.3 5.4 6 0.041 ≤ 0.02
0.4 10.4 3.1 7 0.034 ≤ 0.02
0.5 7.1 2.0 8 ≤ 0.02 ≤ 0.02
0.6 4.3 1.32 10 ≤ 0.02 ≤ 0.02
0.8 2.5 0.76 12 ≤ 0.02
1 1.67 0.49 14 ≤ 0.02
1.5 0.61 0.21 15 ≤ 0.02
2 0.38 0.101 16 ≤ 0.02
2.5 0.24 0.078
Standard current ratings and typical internal resistance values
Authority Voltage ratings Current ratings
3500:
VDE (EN 60934) AC 240 V; DC 65 V 0.05...16 A
CSA, UL AC 250 V; DC 80 V 0.05...16 A
4000:
VDE (EN 60934) AC 240 V; DC 65 V 0.05...10 A
CSA AC 250 V 0.05...10 A
Approvals