https://www.phoenixcontact.com/pi/products/2320380
08/20/2018Page2/4
Energy storage-UPS-CAP/24DC/20A/20KJ-2320380
Technical data
Input data
Nominal input voltage 24 V DC
Input voltage range 18 V DC ... 30 V DC
Current consumption 5 A
Buffer period 12 min. (1 A)
33 s (20 A)
Output data
Nominal output voltage 24 V DC
Setting range of the output voltage (U
Set
)
22 V DC ... 27 V DC
Nominal output current (I
N
)
20 A
POWER BOOST (I
Boost
)
26 A
Connection in series No
Power loss nominal load max. 3.6 W
Output fuse 2x 25 A (internal)
General
IQ technology Yes
Disposal
Used batteries must not be thrown away with household waste, they
should instead be disposed of in accordance with applicable national
regulations. They can also be returned to Phoenix Contact or the
manufacturer.
Net weight 2.9 kg
Memory medium Dual layer capacitor
Protection class III
Degree of protection IP20
> 695000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Standards and Regulations
Connection in acc. with standard CUL
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Shipbuilding approval GL applied for
UL approvals UL/C-UL Recognized UL 60950-1
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm, 15 ... 150 Hz, 2.3g/2.3g according to IEC
60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
Drawings