3300-IG2-P10-10A

Thermal-Magnetic Circuit Breakers 3300/3400
www.e-t-a.de
1629
1
1
Description
Typical applications
Ordering information 3400
Technical data
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Control systems, instrumentation, medical equipment, machine tools,
robotics.
3300 3400
fast acting standard delay
Type No.
3400 standard delay
Mounting
iG2 moulded threadneck M12x1 (bulk-shipped), not with -H;
... leave blank for metal threadneck, required for -H
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
K20 screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
A3 same as main terminals, up to I
N
=7 A max. load 5 A
Manual release (optional)
H manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si with silver-plated solder terminals
(N/O and N/C)
Current ratings
0.05...16 A
3400 - iG2 - P10 - .. - .. - Si - 10 A ordering example, without manual
release and with moulded
threadneck
3400 - ... - P10 - .. - H - Si - 10 A ordering example, with manual
release and metal threadneck
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current ratings 0.05...16 A
Auxiliary circuit 1 A, AC 240 V / DC 65 V
Typical life
with -H: 5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
without -H: 0.05...8 A 5,000 operations at 2 x I
N
, inductive
> 8 A 1,500 operations at 2 x I
N
, inductive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
operating area 2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V double insulation
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7 AC 840 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.05...0.8 A self-limiting
1...2 A 200 A
2.5...16 A 400 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...16 A AC 250 V 1,000 A
0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass 3300: approx. 55 g
3400: approx. 50 g
Ordering information 3300
Type No.
3300 fast acting
Mounting
iG2 moulded threadneck M12x1, > 5 pcs: hex nut and knurled nut
bulk shipped
Terminal design
P10 blade terminals tin-plated DIN 46244-A6.3-0.8
Current ratings
0.05...16 A
3300 - iG2 - P10 - 10 A
Approvals
Authority Standard Rated voltage Current ratings
VDE IEC/EN 60934 AC 240 V
DC 65 V
0.05...16 A
0.05...16 A
UL UL 1077
C22.2 No 235
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
CSA C22.2 No 235 AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
Thermal-Magnetic Circuit Breakers 3300/3400
www.e-t-a.de
1629
2
1
Terminal design 3400
Dimensions
SW14
10
ø6.4
ON
OFF
16
22.5
50.3 (-iG2)
52.3 (-H)
11
M12x1
tightening torque max. 1.5 Nm
14.5
11.4
29
42
ø6.4
10.5
18.5
ON
24.5
OFF
M12x1
ø12.2
-0.1
11.5
-0.1
9.5
±0.2
ø3
+0.2
ø12.5
+0.2
5
current rating in A
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
mounting hole
mounting holes
.886
.630
.252
.394
1.98 (-iG2)
2.06 (-H)
.433
.571
1.65
1.14
.450
.551
.480
-.004
.453
-.004
.413
.252
.965
.728
.374
±.008
.118
+.008
.492
+.008
-iG2-P10
-H (3400 only)
7
.276
-P10-Si
-P10-A3
132
14 26
M3.5x5.5 ISO 1207
tightening torque max. 0.8 Nm
5
1.5
-K20
9
12
.354
.197
.059
Installation drawing
(max. 2 mm/
.079 in. when
fitted with water
splash cover)
operating area
(reinforced insulation)
3
1
3
max. 2.5
3
41
26
mounting area
.118
1.02
.118 .039
max .098
1.61
.118
Internal connection diagrams
line 1
2
I
>
2
3
5
4
7
6
I
>
3 (from I
N
=8 A)
line 1
with shunt terminal (-A3)
and auxiliary contacts (-Si)
3300/3400 3400
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
Standard current ratings and typical internal resistance values
Current
ratings
(A)
Internal resistance
(Ω)
Current
ratings
(A)
Internal resistance
(Ω)
3300 3400 3300 3400
0.05 447 211 3 0.18 0.19
0.1 131 131 4 0.109 0.090
0.2 41 40 5 0.066 0.061
0.3 19.6 19.3 6 0.046 0.041
0.4 10.4 10.4 7 0.032 0.034
0.5 7.2 7.1 8 0.02 ≤ 0.02
0.6 4.8 4.3 10 ≤ 0.02 ≤ 0.02
0.8 2.5 2.5 12 ≤ 0.02 ≤ 0.02
1 1.93 1.67 13 ≤ 0.02 ≤ 0.02
1.5 0.81 0.61 14 ≤ 0.02 ≤ 0.02
2 0.44 0.38 15 ≤ 0.02 ≤ 0.02
2.5 0.27 0.24 16 ≤ 0.02 ≤ 0.02
Thermal-Magnetic Circuit Breakers 3300/3400
www.e-t-a.de
1629
3
1
Thermal-Magnetic Circuit Breakers 3300/3400
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
Ambient temp. °F
°C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.79 0.83 0.88 1 1.08 1.16 1.24
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
Trip time in seconds
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
Type 3400 0.05…7 A AC/DC
1)
1)
Magnetic tripping currents are increased by 20 % on DC supplies.
Type 3400 8…16 A AC/DC
1)
Accessories
Typical time/current characteristics
M12x1 M12x1
For push buttons with M12 moulded threadneck (-iG2)
(not with manual release -H)
Water splash cover,
transparent with knurled nut
X 210 663 01 (IP64)
Hex nut with splash cover,
black
X 200 801 03 with O ring
(IP66 and IP67)
Hex nut with splash cover,
transparent
X 200 801 08 with O ring
(IP66 and IP67)
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
Trip time in seconds
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
Type 3300 0.05…7 A AC/DC
1)
1)
Magnetic tripping currents are increased by 20 % on DC supplies.
Type 3300 8…16 A AC/DC
1)
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
This is a metric design and millimeter dimensions take precedence (
mm
)
inch

3300-IG2-P10-10A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union