Thermal-Magnetic Circuit Breakers 3300/3400
www.e-t-a.de
1629
1
1
Description
Typical applications
Ordering information 3400
Technical data
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Control systems, instrumentation, medical equipment, machine tools,
robotics.
3300 3400
fast acting standard delay
Type No.
3400 standard delay
Mounting
iG2 moulded threadneck M12x1 (bulk-shipped), not with -H;
... leave blank for metal threadneck, required for -H
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
K20 screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
A3 same as main terminals, up to I
N
=7 A max. load 5 A
Manual release (optional)
H manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si with silver-plated solder terminals
(N/O and N/C)
Current ratings
0.05...16 A
3400 - iG2 - P10 - .. - .. - Si - 10 A ordering example, without manual
release and with moulded
threadneck
3400 - ... - P10 - .. - H - Si - 10 A ordering example, with manual
release and metal threadneck
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current ratings 0.05...16 A
Auxiliary circuit 1 A, AC 240 V / DC 65 V
Typical life
with -H: 5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
without -H: 0.05...8 A 5,000 operations at 2 x I
N
, inductive
> 8 A 1,500 operations at 2 x I
N
, inductive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
operating area 2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V double insulation
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7 AC 840 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.05...0.8 A self-limiting
1...2 A 200 A
2.5...16 A 400 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...16 A AC 250 V 1,000 A
0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass 3300: approx. 55 g
3400: approx. 50 g
Ordering information 3300
Type No.
3300 fast acting
Mounting
iG2 moulded threadneck M12x1, > 5 pcs: hex nut and knurled nut
bulk shipped
Terminal design
P10 blade terminals tin-plated DIN 46244-A6.3-0.8
Current ratings
0.05...16 A
3300 - iG2 - P10 - 10 A
Approvals
Authority Standard Rated voltage Current ratings
VDE IEC/EN 60934 AC 240 V
DC 65 V
0.05...16 A
0.05...16 A
UL UL 1077
C22.2 No 235
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
CSA C22.2 No 235 AC 250 V
DC 80 V
0.05...16 A
0.05...16 A