https://www.phoenixcontact.com/pi/products/2807926
08/18/2018Page2/4
Surge protection plug-CT 10-18FS+F/PE-24-2807926
Technical data
General
Color jet black RAL 9005
Standards for cearances and creepage distances VDE 0110-1
Mounting type On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Type LSA-PLUS module
Direction of action Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.00
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
24 V DC
24 V AC
Maximum continuous voltage U
C
40 V DC
28 V AC
Rated current 1.5 A AC (75 °C)
350 mA DC (75 °C)
Operating effective current I
C
at U
C
≤ 5 µA (18x)
Residual current I
PE
≤ 1 µA (19x)
Nominal discharge current I
n
(8/20) µs (line-line)
119 A (per path)
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA (per path)
Nominal discharge current I
n
(8/20) µs (signalground-earth)
5 kA (per path)
Pulse discharge current I
imp
(10/350)µs (line-earth)
2.5 kA
Pulse discharge current I
imp
(10/350)µs (signalground-earth)
2.5 kA
Total discharge current I
total
(8/20)µs
10 kA
Max. discharge current I
max
(8/20) µs maximum (line-line)
119 A (per path)
Max. discharge current I
max
(8/20) µs maximum (line-earth)
5 kA (per path)
Nominal pulse current Ian (10/1000) µs (line-signalground) 23 A
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 650 V
Output voltage limitation at 1 kV/µs (line-signalground) spike ≤ 70 V
Output voltage limitation at 1 kV/µs (line-signalground) static ≤ 60 V
Residual voltage at I
n
(line-earth)
≤ 30 V
Residual voltage at I
n
(line-signalground)
≤ 85 V
Residual voltage with Ian (10/1000) µs (line-signalground) ≤ 65 V
Response time tA (line-signalground) ≤ 1 ns
Response time t
A
(line-earth)
≤ 100 ns
Input attenuation aE, asym. typ. 0.1 dB (≤ 2 MHz / 50 Ω)
typ. 0.1 dB (≤ 200 kHz / 150 Ω)
typ. 0.1 dB (≤ 80 kHz / 600 Ω)