https://www.phoenixcontact.com/us/produkte/3001734
18.10.2012Page2/6
Feed-through terminal block-HDFKV 16-3001734
Technical data
Technical data
Open side panel nein
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Surge voltage test setpoint 7.3 kV
Result of surge voltage test Test passed
Power frequency withstand voltage setpoint 1.89 kV
Result of power-frequency withstand voltage test Test passed
Checking the mechanical stability of terminal points (5 x conductor
connection)
Test passed
Bending test rotation speed 10 rpm
Bending test turns 135
Bending test conductor cross section/weight 0.5 mm² / 0.3 kg
Bending test conductor cross section/weight 16 mm² / 2.9 kg
Bending test conductor cross section/weight 25 mm² / 4.5 kg
Result of bending test Test passed
Conductor cross section tensile test 0.5 mm²
Tractive force setpoint 20 N
Conductor cross section tensile test 16 mm²
Tractive force setpoint 100 N
Conductor cross section tensile test 25 mm²
Tractive force setpoint 135 N
Tensile test result Test passed
Requirements, voltage drop ≤ 3.2 mV
Result of voltage drop test Test passed
Temperature-rise test Test passed
Conductor cross section short circuit testing 16 mm²
Short-time current 1.92 kA
Conductor cross section short circuit testing 25 mm²
Short-time current 3 kA
Short circuit stability result Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Result of thermal test Test passed
Connection data
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 25 mm²
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 16 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 4
Conductor cross section stranded, with ferrule without plastic
sleeve min.
0.5 mm²