https://www.phoenixcontact.com/us/products/3210269
10/20/2015Page2/4
Disconnect terminal block-PTT 2,5-2TG BU-3210269
Technical data
General
Overvoltage category III
Insulating material group I
Connection in acc. with standard IEC 60947-7-1
Maximum load current
16 A (In case of a 4 mm² conductor cross section, the maximum load
current must not be exceeded by the total current of all connected
conductors.)
Nominal current I
N
16 A (with 4 mm² conductor cross section)
Nominal voltage U
N
400 V
Open side panel ja
Dimensions
Width 5.2 mm
End cover width 0.8 mm
Length 92.4 mm
Height 45.80 mm
Height NS 35/7,5 47.4 mm
Height NS 35/15 54.9 mm
Connection data
Connection method Push-in connection
Connection in acc. with standard IEC 60947-7-1
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 26
Max. AWG conductor cross section, flexible 14
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
sleeve, max.
0.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Stripping length 10 mm
Internal cylindrical gage A3