Type 2 surge protection connector-F-MS 12/ST-2817990
Technical data
Standards
Height 52.5 mm
Depth 55.5 mm
Pitch unit 1 Div.
Protective circuit
IEC category II
IEC category T2
EN type T2
Nominal voltage UN 230 V AC
Nominal DC sparkover voltage Uagn 500 V ±20 %
Arrester rated voltage UC 260 V AC
Arrester rated voltage UC (N-PE) 260 V AC
UT (TOV-proof) 1200 V AC (200 ms / N-PE)
Nominal frequency fN 50 Hz
Nominal frequency fN 60 Hz
Ground conductor current IPE ≤ 1 µA
Standby power consumption PC 0.3 mVA
Max. discharge surge current Imax (8/20) µs 40 kA
Max. discharge surge current Imax (8/20) µs maximum (N-PE) 40 kA
Nominal discharge surge current In (8/20) µs 20 kA
Nominal discharge surge current In (8/20) µs (N-PE) 20 kA
Lightning test current (10/350) µs, charge 6 As
Lightning test current (10/350) µs, peak value limp 12 kA
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) ≤ 1.5 kV
Insulation resistance Riso: > 1 GΩ
Protection level Up ≤ 1.5 kV
Protection level UP (N-PE) ≤ 1.5 kV
Residual voltage ≤ 150 V (at 5 kA)
Residual voltage (N-PE) ≤ 150 V (at 5 kA)
Residual voltage (N-PE) ≤ 400 V
Residual voltage (N-PE) ≤ 250 V (at 10 kA)
Residual voltage (N-PE) ≤ 100 V (at 3 kA)
Response time ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Follow current quenching capacity If (N-PE) 100 A (260 V)
Connection, protective circuit
Connection type IN FLASHTRAB/VALVETRAB plug-in system
Connection type OUT FLASHTRAB/VALVETRAB plug-in system
Standards
Standards/regulations IEC 61643-1 2005
Standards/regulations EN 61643-11/A11 2007