ECSR1.6

1
BULLET
CLASS RK5
DUAL ELEMENT TIME-DELAY FUSES
AMPERE RATINGS
ECNR 250V
0.1 1.12 3.2 10 60 225
0.12 1.25 3.5 12 70 250
0.15 1.4 4 15 75 300
0.2 1.5 4.5 17.5 80 350
0.25 1.6 5 20 90 400
0.3 1.8 5.6 25 100 450
0.4 2 6 30 110 500
0.5 2.25 6.25 35 125 600
0.6 2.5 7 40 150
0.8 2.8 8 45 175
1 3 9 50 200
ECSR 600V
0.1 1.25 3.5 12 70 250
0.15 1.4 4 15 75 300
0.2 1.5 4.5 17.5 80 350
0.25 1.6 5 20 90 400
0.3 1.8 5.6 25 100 450
0.4 2 6 30 110 500
0.5 2.25 6.25 35 125 600
0.6 2.5 7 40 150
0.8 2.8 8 45 175
1 3 9 50 200
1.12 3.2 10 60 225
ECNR/ECSR SPECIFICATIONS
Dual-Element Time-Delay
Voltage Rating: ECNR - 250VAC, ECSR - 600VAC
Ampere Rating: .1 - 600 Amps
Interrupting Rating: 200,000 RMS Symmetrical Amps
Current Limiting: RK5 Fuse
Agency Approvals:
UL Listed, Class RK5, Guide JDDZ, File E162363
CSA Certified HRCI-R per C22.2, No. 248.12
Self-Certified DC Ratings:
Voltage Rating: ECNR (.1-600) 125VDC
ECSR (.1-600) 300VDC
Interrupting Rating: ECNR/ECSR 20,000 Amperes DC
RECOMMENDED FUSEBLOCKS:
Refer to page 136 in this catalog.
RECOMMENDED UPGRADE:
Class RK1 (LENRK/LESRK) for greater degree of short cir-
cuit protection.
Catalog Number ECNR (.1 - 600A) 250 Volts AC or Less
Catalog Number ECSR (.1 - 600A) 600 Volts AC or Less
CROSS REFERENCE
VOLTS EDISON BUSSMANN GOULD LITTELFUSE
250 ECNR FRN-R TR FLNR
600 ECSR FRS-R TRS FLSR
BENEFITS:
True dual - element construction allows sizing of 125%
FLA for motor backup protection.
Superior overload and cycling capabilities.
Current limiting; provides component short-circuit protec-
tion.
APPLICATIONS:
Recommended for AC power distribution system mains,
feeders, and branch circuits.
Protection of motors and motor branch circuits.
Protection of transformers and other inductive loads.
All general - purpose applications including lighting, heat-
ing and other non-inductive loads.
characteristics of these fuses typically allows them to be
sized closer to the running ampacity of inductive loads to
reduce cost and provide improved overcurrent protection.
These fuses will override normal equipment current surges
to reduce unnecessary fuse openings. They are the most
popular fuses used in the industry and the most economical
for most applications, especially motors and transformers.
They have moderate current limitation.
2
BULLET
CLASS RK5
DUAL ELEMENT TIME-DELAY FUSES
ECNR/ECSR dual element FUSES
These fuses are recommended for AC power distribution
system mains, feeders and branch circuits having inductive
loads (motors, transformers) or non-inductive loads (light-
ing, heating) where the available short-circuit current does
not exceed 200,000 RMS symmetrical amperes. These
“dual element, time-delay” fuses have minimum industry
standard time-delay of 10 seconds at 5 times the fuse rating
(8 sec. minimum for 250V, 30A and less). The time-delay
Overall Max
Catalog Length Diameter
Number Amps A B
0-30 2 .56"
35-60 3 .81"
ECNR 70-100 5.88" 1.06"
250V 110-200 7.13" 1.56"
225-400 8.63" 2.06"
450-600 10.38" 2.59"
0-30 5 .81
35-60 5.5 1.06
ECSR 65-100 7.88 1.11
600V 110-200 9.63 1.61
225-400 11.63 2.34
450-600 13.38 2.88
(1)
Dimensions in inches.
CLASS R FUSES WILL FIT CLASS H, K AND R FUSE CLIPS. CLASS R FUSE CLIPS WILL ONLY ACCEPT CLASS R
FUSES. FUSES RATED 600 VOLTS AC OR LESS MAY BE APPLIED AT ANY LOWER VOLTAGE. CONTACT EDISON
FUSEGEAR FOR SPECIAL PRODUCTS OR APPLICATIONS.
DIMENSIONS
(1)
Ferrule Design–0 through 60 Amperes Knife Blade–70 through 600 Amperes
BULLET
CLASS RK5
DUAL ELEMENT TIME-DELAY FUSES
AMPERE
RATING
RMS SYMMETRICAL CURRENTS IN AMPERES
1,000
100
10
10,000
600A
10
100
TIME IN SECONDS
1
.1
.01
20,000
400A
200A
100A
60A
30A
15A
10A
AMPERE
RATING
RMS SYMMETRICAL CURRENTS IN AMPERES
10
1
.1
100
6.125A
10
100
TIME IN SECONDS
1
.1
.01
3.2A
1.125A
.6A
.3A
.2A
.1A
600
.4A
.8A
.5A
1A
1.6A
2A
2.5A
4A
5A
AVERAGE TIME/CURRENT CURVES
Cat No. ECNR (AMP) 250 VAC
3

ECSR1.6

Mfr. #:
Manufacturer:
Description:
Industrial & Electrical Fuses UL CLASS RK-5 TIME DELAY
Lifecycle:
New from this manufacturer.