IB IL 24 EDO 2 (-PAC)
10 6528B
Output current with ground connection
interrupted
In the event of ground connection interrupt the
outputs can be set as usual.
Detection of open circuit and of short circuit is
functioning correctly.
Switching power with ground connection
interrupted
Inrush current 1.5 A for 20 ms, maximum (typical)
Digital Outputs (Continued)
Output Characteristic Curve When Switched On (Typical)
Output Current (A) Differential Output Voltage (V)
00
0.2 0.047
0.3 0.069
0.5 0.114
0.7 0.159
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
Where
P
TOT
Total power dissipation of the terminal
n Index of the number of set outputs n = 1 to 2
I
Ln
Load current of the output n
Power dissipation of the housing P
HOU
0.7 W
(within the permissible operating temperature)
P
E L
= 0 , 3 W +
Σ
( 1 5 0 m W + I
L n
2
x 0 , 1 5
)
n = 1
2
Limitation of Simultaneity, Derating
None
Safety Measures
Overload/short circuit in segment circuit Electronic
Surge voltage Protective circuits of the power terminal
Polarity reversal Protective circuits of the power terminal
IB IL 24 EDO 2 (-PAC)
6528B 11
Electrical Isolation/Isolation of the Voltage Areas
To provide electrical isolation between the logic level and the I/O area, it is necessary to
supply the station bus terminal and the digital output terminal described here using the
bus terminal or a power terminal from separate power supply units. Interconnection of the
24 V power supplies is not permitted.
Common Potentials
The 24 V main voltage supply, 24 V segment voltage, and GND have the same potential.
FE is a separate potential area.
Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O
Terminal
- Test Distance - Test Voltage
5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min
5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min
7.5 V supply (bus logic)/24 V supply (I/O) 500 V AC, 50 Hz, 1 min
24 V supply (I/O)/functional earth ground 500 V AC, 50 Hz, 1 min
Error Messages to the Higher-Level Control or Computer System
Short circuit/overload of an output Yes
An error message is generated when an output is shorted and switched on. In addition a
status bit is set in the input process data (see Page 5) and on the terminal block the
diagnose LED (D) flashes at 2 Hz (medium).
Open circuit Yes;
In addition a status bit is set in the input process
data (see Page 5) and on the terminal block the
diagnose LED (D) flashes at 2 Hz (medium).
Operating voltage out of range No
IB IL 24 EDO 2 (-PAC)
12 6528B
© Phoenix Contact 06/2002 Technical modifications reserved TNR ^90 10 08 5
Phoenix Contact GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
+ 49 - (0) 52 35 - 3-00
+ 49 - (0) 52 35 - 3-4 12 00
www.phoenixcontact.com
Worldwide locations:
www.phoenixcontact.com/salesnetwork
Ordering Data
The documentation can be downloaded free of charge at the following address:
www.phoenixcontact.com
.
Description Order Designation Order No.
Inline terminal with two digital outputs and
extended diagnostics
including connectors and labeling field
IB IL 24 EDO 2-PAC 28 61 61 6
Inline terminal with two digital outputs and
extended diagnostics
IB IL 24 EDO 2 27 42 59 9
One of the listed connectors is needed for the complete fitting of the IB IL 24 EDO 2
terminal.
I/O connector with eight terminals, spring-clamp
connection (green, w/o color print);
pack of 10
IB IL SCN-8 27 26 33 7
I/O connector with eight terminals, spring-clamp
connection (green, with color print);
pack of 10
IB IL SCN-8-CP 27 27 60 8
"Configuring and Installing the INTERBUS Inline
Product Range" User Manual
IB IL SYS PRO UM E 27 45 55 4

2861616

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules IB IL 24 EDO 2-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet