460-L

© 2016 Littelfuse Protection Relays & Controls
Protection Relays
Voltage Monitoring Relays
www.littelfuse.com/460
Rev: 1-A-062816
3-Phase Voltage Monitor
460 SERIES
Wiring Diagram
TYPICAL WIRING DIAGRAM FOR MODEL 460 WITH MOTOR CONTROL
Ordering Information
MODEL VOLTAGE DESCRIPTION
460 190-480VAC Automatically senses line voltage, adjustable 1-30 second trip delay, 1-500 second restart delay, and 2-8% voltage unbalance trip point
460-L 190-480VAC Fixed 4 second trip delay and 1 second for single-phase faults, and fixed 6% voltage unbalance trip point
460-14 190-480VAC
Equipped with 2 sets of contacts: Form A (NO) and Form B (NC). Used for applications requiring 2 different voltages such as 5VDC
for a PLC input and 115VAC for an alarm
460-575 475-600VAC Commonly used in Eastern Canada and on generator units that generate 600 VAC power
460-575-14 475-600VAC
Commonly used in Eastern Canada and on generator units that generate 600 VAC power. Equipped with 2 sets of contacts: Form A
and Form B
460-15 190-480VAC
Equipped with 2 sets of Form A (NO) contacts. Used on applications where two different units are to be controlled at once such as a
unit that has separate contacts for a compressor and a fan
460-MR 190-480VAC
Equipped with a 2-prong connection for a normally open push button mounted outside the panel. Used in applications requiring an
external manual reset button
460-VBM 190-480VAC Fixed 6% voltage unbalance trip point. User adjustable low and high voltage trip points
460-400HZ 190-480VAC For use with 400Hz power supply
460-OEM 190-480VAC Bulk package of 460, 20 units
460L-OEM 190-480VAC Bulk package of 460-L, 20 units
Description
The 460 is a 3-phase voltage monitor that protects 190-480VAC
or 475-600V, 50/60Hz motors regardless of size. The product
provides a user selectable nominal voltage setpoint and the
voltage monitor automatically senses line voltage.
This unique microcontroller-based voltage and phase-sensing
device constantly monitors the 3-phase voltages to detect
harmful power line conditions such as low, high, and unbalanced
voltage, loss of any phase, and phase reversal. When a
harmful condition is detected, the MotorSaver
®
output relay
is deactivated after a specified trip delay. The output relay
reactivates after power line conditions return to an acceptable
level for a specified amount of time (restart delay). The trip and
restart delays prevent nuisance tripping due to rapidly fluctuating
power line conditions.
All 460 models feature adjustable 1-30 second trip delay, 1-500
second restart delay, 2-8% voltage unbalance trip point, and one
form C contact except where noted below.
Features & Benefits
FEATURES BENEFITS
Auto-sensing wide
voltage range
Automatically senses system voltage between 190
- 480VAC or 475-600VAC. Saves set-up time
Adjustable trip & restart
delay settings
Prevent nuisance tripping due to rapidly fluctuating
power line conditions
Microcontroller
based circuitry
Improved accuracy and higher reliability
Advanced LED
diagnostics
Quick visual indicator for cause of trip and relay status
Adjustable voltage
unbalance trip setting
Provides reliable protection when regenerative
voltage is present
© 2016 Littelfuse Protection Relays & Controls
Protection Relays
Voltage Monitoring Relays
www.littelfuse.com/460
Rev: 1-A-062816
Ambient Temperature Range
Operating -20° to 70°C (-4° to 15F)
Storage -40° to 8C (-40° to 176°F)
Maximum Input Power 6 W
Class of Protection IP20, NEMA 1 (finger safe)
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Terminal Torque 4.5 in.-lbs.
Wire Type Stranded or solid 12-20 AWG, one per terminal
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air
RFI, Radiated 150 MHz, 10V/m
Fast Transient Burst IEC 61000-4-4, Level 3,
3.5kV input power and controls
Surge
IEC IEC 61000-4-5, Level 3, 4kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance
to a level of 6kV line-to-line
Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute)
Safety Marks
UL UL508 (File #E68520)
CE IEC 60947-6-2
Enclosure Polycarbonate
Dimensions H 88.9 mm (3.5”); W 52.9 mm (2.08”);
D 59.69 mm (2.35”)
Weight 0.7 lb. (11.2 oz., 317.51 g)
Mounting Method 35 mm DIN rail or Surface Mount
(#6 or #8 screws)
460-MR (manual reset) External NO pushbutton required.
Specifications
Frequency 50/60Hz
Low Voltage (% of setpoint)
Trip 90% ±1%
Reset 93% ±1%
High Voltage (% of setpoint)
Trip 110% ±1%
Reset 107% ±1%
Voltage Unbalance (NEMA)
Trip 2-8% adjustable
Reset Trip setting minus 1% (5-8%)
Trip setting minus 0.5% (2-4%)
460L 6% UB fixed (4.5% reset)
Trip Delay Time
Low, High and
Unbalanced Voltage 1-30 seconds adjustable
460L 4 seconds fixed
Single-Phase Faults
(>25% UB) 1 second fixed
Restart Delay Time
After a Fault 1-500 seconds adjustable
After a Complete Power Loss 1-500 seconds adjustable
Output Contact Rating
Form C
Pilot Duty 480VA @ 240VAC, B300
General Purpose 10A @ 240VAC
Form A & Form B
Pilot Duty 360VA @ 240VAC, B300
General Purpose 8A @ 240VAC
460 SERIES

460-L

Mfr. #:
Manufacturer:
Littelfuse
Description:
Industrial Relays 200-480VAC 2-800A SPDT 3PH V MON RELAY
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union