E5ZE-8VVD1VVB-V2 E5ZE-8VVD1VVB-V2
7
Dimensions
Unit: mm (inch)
J E5ZE-8VVD1VVB-V2
Mounting hole
dimensions
Four, M4
Mounting
bracket
Mounting
bracket
253
(9.96)
223
(8.78)
243
(9.57)
243±0.4
(9.96)
40±0.2
(1.57)
60
40
65
(2.56)
145 (5.71)
173.5 (6.83)
Optional mounting
bracket position
85.5
(3.37)
Precautions
J MOUNTING THE CONTROLLERS
Side-by-side, Close Mounting
Saves space and improves wiring efficiency.
Control panel
Up
Wall Mounting
Can be mounted to places with limited depth.
Control panel
Up
General Mounting Precautions
The side of the E5ZE with the terminal block and connectors
must not face up, otherwise operating errors may result.
Prepare four M4 screws to mount the E5ZE to control panels.
Use flat washers and spring washers with screws to mount the
E5ZE to control panels so that the screws will not loosen.
The mounting brackets must be attached to the E5ZE with the
four M3 x 6 screws provided with the E5ZE and each of the
screws should be tightened to a torque of 0.43 to 0.58 N S m, or
4.4 to 5.9 kgf S cm.
Do not mount as shown in the following diagram.
Control panel
Up
J WIRING DEVICENET CONNECTORS
The following diagram shows how the DeviceNet connector
XW4B-05C1-H1-D is wired. Multi-drop connections cannot be
used with this connector. The connector is color-coded to match
the insulating sheath of each conductor.
Black (V--)
Blue (CAN L)
Shield
White (CAN H)
Red (V+)