TAC-250-103

TAC series(200,250,300A)
Three phase input type(1-stage filter)
TAC -200 -223 -O
Ordering information
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
Leakage Current
(Input 250/500V 60Hz)
Line to ground
capacitor
(nominal value)
103 1.0mA/2.0mA max 10,000pF
223 2.5mA/5.0mA max 22,000pF
333 3.5mA/7.0mA max 33,000pF
*
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4 Option
U:Improve differential mode attenuation
(Rated voltage 250V)
1 2 3 4
Features of TAC series
Circuit Diagram Derating Curve
High-attenuation type of common mode noise from 150kHz to 1MHz (1-stage filter)
- Three phase rated voltage 500 VAC (voltage range:528V max)
- Selectable leakage current value
R
Specifications
No. Items TAC-200-223 TAC-250-223 TAC-300-223
1 Rated Voltage[V] AC Three Phase 500 (voltage range:528 max) 50/60Hz
*1
2 Rated Current[A] 200 250 300
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100M
W
min at room temperature and humidity
5 Leakage current 250/500V 60Hz 2.5mA/5.0mA max
6 DC resistance 2m
W
max 1.5m
W
max 1m
W
max
7 Safety agency approval temperatures -25 to +85
C
(Refer to Derating Curve)
8 Operating temperature -40 to +85
C
(Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85
C
/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s
2
(2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s
2
(20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
14 Case size (without projection) 190
X
110
X
360 mm [7.48
X
4.33
X
14.17 inches]
(W
X
H
X
D)
15 Weight 8.0kg max
*1 Only “TAC-OOO-OOO-U”, Three Phase 250 (275 max)
*Keep free ventilation holes for cooling.
Ambient Temperature [C]
Load Factor [%]
70 80 90-20 40 50 60
20
0
-40 -30
100
80
60
40
LOAD
Case
LINE
4
5
6
1
2
3
CY : Line to ground capacitor
CY CY
CY
CY CY
CY
: Mounting Plate
LOAD
Case
LINE
4
5
6
1
2
3
CY : Line to ground capacitor
CY CY
CY
CY CY
CY
: Mounting Plate
TA-21
(1) TAC-OOO-OOO
(2) TAC-OOO-OOO-U (Option : U)
TAC series (200,250,300A)
External view
Protection Earth
Mounting Hole
Terminal Cover
Mounting Hole
Terminal
Input
Mounting Plate
Protection Earth
Terminal
Output
Name Plate
Can not be mounted upside-down.
(mounted the top surface)
Tolerance : ±1 [±0.04]
Weight : 8.0kg max
Mounting Plate : Stainless steel t=2.0 [0.08]
Dimensions in mm, [ ]=inches
Terminal block screw tightening torque M10 : 14.2N-m (144.9kgf-cm) max
Protection Earth screw tightening torque M8 : 9.2N-m (93.9kgf-cm) max
3-M10
3-M10
M8
3-f6.5
M8
42
190
[7.48]
[1.65]
[1.46]
[0.26]
[0.26]
[0.26]
[6.3]
160
±0.5
340
±0.5
282.5
37
6.5
6.5
6.5
110
360
[14.17]
[4.33]
[3.29]
[11.12]
[13.39]
[0.26]
83.5
TA-22

TAC-250-103

Mfr. #:
Manufacturer:
Cosel
Description:
AC Power Line Filters Power Line Filters 3Phase 500VAC 250A 10,000pF EMI filte
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS