Phoenix Contact page 2 of 5
Fuse Modules EMG 22-SI
2. Technical Data for EMG 22-SI
solid flexible I U
[mm
2
]AWG[A] [V]
Connection data 0.2 - 4 0.2 - 2.5 25 - 12 * 250
* The current is determined by the fuse.
Description
Fuse module
For 3 G fuse links
5 x 20 mm (0.197 x 0.787 in.)
Individual connection
Common centralized point
Device marker
Technical Data
Maximum voltage
Fuse links
1
) (between two terminal blocks)
Fuse links
1
) (for simultaneous load of the links)
General Data
Ambient operating temperature range
Standards/specifications
Mounting position
Mounting
Connection type
1
)The values specified only apply for G fuse links from Wickmann.
EMG 22-SI
With 3 G fuse holders
Module width 22.5 mm (0.886 in.)
Type Order No.
Pcs.
Pkt.
EMG 22-SI3E
EMG 22-SI3S
29 52 27 9
29 55 77 1
10
EMG-GKS 29 47 03 5
50
250 V AC
6.3 A/250 V AC, maximum
3 A/250 V AC, maximum
-20°C to +50°C (-4˚F to +122˚F)
IEC 664/IEC 664 A/DIN VDE 0110-1:1989-01,
degree of pollution 2, Surge Voltage Category III;
DIN VDE 0109-11:1987-12, draft
DIN VDE 0160:1988-05
Any
Can be mounted without spacing
Screw connection
75 mm (2.953 in.)
62 mm
(2.441 in.)
2
468
1
357
L
LL5
1
234
EMG 22-SI3E
EMG 22-SI3S
M 3
8 mm
(0.31 in.)