2740818

PHOENIX CONTACT Deutschland GmbH Page 1 / 6
http://www.phoenixcontact.de Feb 8, 2011
Extract from the online
catalog
IB IL AI 2/SF-230
Order No.: 2740818
The illustration shows version IB IL AI 2/SF
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818
Inline analog input terminal block, without accessories, 2 inputs, 0-20
mA, 4-20 mA, ±20 mA, 0-10 V, ±10 V, 3 dB base frequency at 230 Hz,
2-wire connection method
Commercial data
GTIN (EAN)
4 017918 574789
sales group K412
Pack 1 pcs.
Customs tariff 85389091
Catalog page information Page 72 (AX-2007)
Product notes
WEEE/RoHS-compliant since:
08/29/2008
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The analog Inline input terminals are suited for connecting conventional sensors for the acquisition of current and voltage
signals.
Particular features of the modules are:
- High accuracy of measurement
- Extremely rapid acquisition of measurement values
IB IL AI 2/SF-230 Order No.: 2740818
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 8, 2011
- Excellent noise suppression and common mode rejection, and
- Measurement value acquisition with a resolution of 16 bits
It goes without saying that you also have advantages in handling with the analog Inline input terminals, such as multi-
wire connection or the automatic contact with the grounding conductor when the terminal is snapped onto the DIN rail.
The Inline terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the proven ZBFM-6... Zack strip for labeling the terminal points.
Technical data
General data
Width 12.2 mm
Height 136.8 mm
Depth 71.5 mm
Weight 47 g
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
7.5 V supply (bus logic), 24 V supply U
ANA
/ I/O 500 V AC 50 Hz 1
min
7.5 V supply (bus logic), 24 V supply U
ANA
/functional earth ground
500 V AC 50 Hz 1 min
I/O / functional earth ground 500 V AC 50 Hz 1 min
Interface
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 kbps
500 kBit/s
Transmission physics Copper
IB IL AI 2/SF-230 Order No.: 2740818
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 8, 2011
Inline potential routing
Communications power U
L
7.5 V DC (via voltage jumper)
Current consumption from U
L
max. 60 mA
Typ. 45 mA
Current consumption from U
M
0 A DC
Current consumption from U
S
0 A DC
I/O supply voltage U
ANA
24 V DC
Current consumption from U
ANA
max. 18 mA
Typ. 13 mA
Analog inputs
Number of inputs max. 2 (single ended)
Connection method 2-wire (shielded)
Input name Analog inputs
A/D conversion time 120 µs (per channel)
Resolution A/D 16 bit
Limit frequency (3 dB) 40 Hz
230 Hz
Data formats IL, IB ST, IB RT, standardized display
Measured value representation 16 bits (15 bits + sign bit)
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Voltage input signal 0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input < 220 kΩ
Precision 0.02 %
Number of inputs 2 (single-ended voltage inputs)
Voltage input signal 0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input 220 kΩ
Number of inputs 2 (single-ended current inputs)
Current input signal 0 mA ... 40 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input 50 Ω 0.02 %

2740818

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL AI 2/SF 230
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet