BP/T-10

Edison base plug fuses – dual-element,
time-delay, 125 volts, up to 30 amps
Catalog symbol:
•
T - (amps)
•
BP/T - (amps)
Description:
Bussmann
®
series dual-element, time-delay
Edison style plug fuse.
Specications:
Ratings
•
Volts — 125 Vac or less
•
Amps — 3/10 to 30 A
•
Interrupting rating — 10 kA RMS Sym
Agency Information
•
UL
®
Listed (up to 6-1/4 A), Std. 248-11, Guide
JFHR, File E56412, (7 to 30 A) Guide JEFV,
File E12112
•
CSA
®
Certified, Class 1423-01, File 53787
•
CE
Catalog numbers (amps)
T - 3/10 T - 2-1/4 T - 7
T - 4/10 T - 2-1/2 T - 8
T - 1/2 T - 2-8/10 T - 9
T - 6/10 T - 3 T - 10
T - 8/10 T - 3-2/10 T - 12
T - 1 T - 3-1/2 T - 14
T - 1-1/8 T - 4 T - 15
T - 1-1/4 T - 4-1/2 T - 20
T - 1-4/10 T - 5 T - 25
T - 1-6/10 T - 5-6/10 T - 30
T - 1-8/10 T - 6
T - 2 T - 6-1/4
Package quantity and weight
Amp
ratings
Quantity Weight
Per
box
Per
card
Per
box
Per 5
cards
3/10 to 14 A 4 1 0.210 0.46
15 to 30 A 4 3 0.25 1.07
Features:
•
Heavy duty time-delay plug fuse
•
Use to protect critical motor circuits or
motors that cycle on/off frequently
•
An industrial/commerical grade product with
exclusive dualelement construction
•
Edison base size
•
These fuses thread into fuse receptacles and
box cover units
•
Industrial strength, featuring an exclusive
dual-element construction
•
This spring loaded design provides superior
short circuit and overload protection
•
More time-delay than the medium duty Type
TL fuses in order to better protect industrial
motors and critical residential circuits
Recommended fuse holders
Catalog
numbers
Type
box
Catalog
numbers
Type
box
SOU
2 1/4”
handy
SOY
4”
square
SRU SRY
SSU SSY
SOW
2 3/4”
handy
SSY-RL
SRW STY
SSW SCY
SOX
4”
octagon
SOY-B
SRX SSN
Single
gang
Technical Data 1034
Effective May 2016
Supersedes December 1998
BUSSM ANN
SERIES
TechnicalData1034
Effective May 2016
For Eatons Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
CSA is a registered trademark of the
Canadian Standards Group.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. 1034 – SB98107
May 2016
Follow us on social media to get the
latest product and support information.
Edison base plug fuses
dual-element, time-delay, 125 volts, up to 30 amps
The only controlled copy of this Data Sheet is the electronic read-only version located on the Eaton Network Drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
ofany products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
10
100
1000
2000
4
100
10
1
0.1
0.01
15
20
30
Time in seconds
Current in amps
Amp
rating
Time-current curve – average melt

BP/T-10

Mfr. #:
Manufacturer:
Description:
Specialty Fuses FUSETRON PLUG FUSE
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union