https://www.phoenixcontact.com/pi/products/2866019
08/20/2018Page2/4
Monitoring relay-EMD-SL-C-OC-10-2866019
Technical data
Ambient conditions
Ambient temperature (storage/transport) -25 °C ... 70 °C
Input data
Input current range 0 mA ... 100 mA (Connection terminals: I1 and GND)
0 A ... 1 A (Connection terminals: I2 and GND)
0 A ... 10 A (Connection terminals: I3 and GND)
Overload capacity
800 mA (at I
N
= 100 mA)
3 A (at I
N
= 1 A)
12 A (at I
N
= 10 A)
Maximum temperature coefficient < 0.1 %/K
Function Overcurrent
Min. setting range
5 % ... 95 % (from I
N
)
Max. setting range
10 % ... 100 % (from I
N
)
Setting range for response delay 0.2 s ... 10 s
Basic accuracy ± 5 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Recovery time 500 ms
Contact side
Contact type 1 floating PDT
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse 5 A (fast-blow)
Power supply
Supply voltage range 24 V AC ... 230 V AC (see Power modules)
24 V DC (see Power modules)
General
Mechanical service life
approx. 2x 10
7
cycles
Operating mode 100% operating factor
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Overvoltage category III, basic insulation (as per EN 50178)
Housing insulation material Polyamide PA, self-extinguishing
Color green
Rated insulation voltage 300 V (acc. to EN 50178)
Conformance CE-compliant
UL, USA/Canada UL/C-UL listed UL 508